Wiring Inputs And Outputs - United Technologies Carrier Unit Vent Open Integration Manual

Unit ventilator integration
Table of Contents

Advertisement

Wiring inputs and outputs

Wiring inputs and outputs
I/O
Type
Zone Temp/
AI
Zone Temp*
AI
RAT or CO
2
Sensor
SAT Sensor
AI
OAT Sensor
AI
Changeover Temp AI
Input Channel #5
BI
Freezestat
BI
OA Damper
AO
Valve / F&B
AO
Cooling Valve
AO
Fan High Spd
BO
Fan Med Spd
BO
Fan G / Low Spd
BO
BO-4
BO
BO-5
BO
Legend
AI
AO
- Analog Input
- Analog Output
BI
BO
- Binary Input
- Binary Output
NOTE
Connect ZS or SPT sensor to the Rnet port.
* These outputs are configurable.
Unit Ventilator
Integration Guide
I/O
Gnd
Terminal
Terminal
Rnet
Gnd
Space Temperature - Prime Variable
IN-1
2 - Gnd
Return Air Temperature
Optional IAQ sensor
IN-2
4 - Gnd
Supply Air Temperature
IN-3
6 - Gnd
Outdoor Air Temperature
IN-4
8 - Gnd
Changeover switch
Changeover sensor
IN-5
1 - Gnd
Remote Occ Contact
Fan Status
IN-6
1 - Gnd
Low Limit Thermostat
AO-1
2 - Gnd
Mixed Air Damper
AO-2
4 - Gnd
Face & Bypass Damper
Heating Valve
2-Pipe H/C Valve
AO-3
6 - Gnd
Cooling Valve
BO-1*
1 - Pwr
High Speed Fan
Stage 2 EH
BO-2*
1 - Pwr
Medium Speed Fan
Stage 3 EH)
BO-3
1 - Pwr
Low Speed Fan
BO-4*
1 - Pwr
2-Pipe/2-Pos Valve (for equip w/F&B)
2-Pos Heating Valve (for equip
w/F&B)
EH stage 1
BO-5*
1 - Pwr
2-Pos Cooling Valve (for equip w/F&B)
DX stage 1
EH stage 1 (w/2-Pipe/Electric Heat)
Point Name/
Function
2
Hardware/
Jumper
Position of
Signal
Pins
Communicating
N/A
10K Thermistor
IN-1 Top
0-5 Vdc
IN-1 Bottom
10K Thermistor
IN-2
Top
10K Thermistor
N/A
Dry Contact
N/A
Thermistor
Dry Contact
N/A
Dry Contact
N/A
0-10 Vdc
N/A
2-10 Vdc
0-10 Vdc
N/A
0-10 Vdc
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
Relay
N/A
CARRIER CORPORATION ©2019