Network Points List For N2 And Lonworks - United Technologies Carrier Unit Vent Open Integration Manual

Unit ventilator integration
Table of Contents

Advertisement

Appendix A: Unit Vent Network Points List

Network points list for N2 and LonWorks

Point Name
Point
Access
Return Air
R
Temperature
Setpoint
R/W
Setpoint
R/W
Setpoint
R/W
Setpoint
R/W
Supply Fan Status
R
Supply Air
R
Temperature
Cooling Lockout
R/W
Temperature
Cooling Output
R
Damper Lockout
R/W
Temp
Damper Output
R
Damper Setpoint
R/W
Override Value
Economizer Purge
R/W
Min Pos
Effective Cool
R
Setpoint
Effective Heat
R
Setpoint
Filter Service
R/W
Alarm Timer
Heating Lockout
R/W
Temperature
Heating Output
R
Occ Override Delay R/W
Outdoor Air
R
Temperature
Override Time
R
Remaining
Power Fail Restart
R/W
Delay
Setpoint
R
Adjustment
Setpoint
R/W
Adjustment Range
Space
R
Temperature -
Prime Variable
System Outdoor Air R/W
Unit Ventilator
Integration Guide
Units
Default
Value
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
Off
On
°F
°F
°F
°F
%
%
°F
°F
%
%
°F
°F
%Open
%Open
°F
°F
°F
°F
hr
hr
°F
°F
%
%
min
min
°F
°F
min
min
seconds
seconds
°F
°F
°F
°F
°F
°F
°F
°F
N2
N2 Network
N2 Network
Point Type
Point Address
ADF
50
ADF
4
ADF
9
ADF
7
ADF
8
BI
24
ADF
49
ADF
16
ADF
14
ADF
15
ADF
74
ADF
19
ADF
5
ADF
22
ADF
23
ADF
28
ADF
29
ADF
26
ADF
47
ADF
38
ADF
41
ADF
58
ADF
44
ADF
45
ADF
48
ADF
54
32
LonWorks
SNVT Type
SNVT Name
nvoRtnAirTmp
Output (active) -
default
nviOccCoolSP
Input (passive) -
default
Input (passive) -
nviOccHeatSP
default
nviUnoccClSP
Input (passive) -
default
nviUnoccHtSP
Input (passive) -
default
nvoFanStatus
Output (active) -
default
Output (active) -
nvoSAT
default
nviClLckTemp
Input (passive) -
default
nvoCoolOut
Output (active) -
default
nviDmpLckTmp
Input (passive) -
default
nvoOAVntDmpr
Output (active) -
default
nviDmpSetOvr
Input (passive) -
default
nviEcnPrgMin
Input (passive) -
default
Output (active) -
nvoEffCoolSP
default
nvoEffHeatSP
Output (active) -
default
nviFltAlmTm
Input (passive) -
default
nviHtLckTmp
Input (passive) -
default
Output (active) -
nvoHeatOut
default
nviOccOvrDly
Input (passive) -
default
nvoOAT
Output (active) -
default
nvoOvrTmRem
Output (active) -
default
Input (passive) -
nviUntStrDly
default
nvoSPAdjust
Output (active) -
default
nviSPAdjRng
Input (passive) -
default
nvoSpaceTemp
Output (active) -
default
nviSysOAT
Input (passive) -
CARRIER CORPORATION ©2019