Communications wiring
BACnet ARC156
To set up the Unit Vent for BACnet ARC156
Turn off the power for the Unit Vent by disconnecting power terminals.
1
Using the rotary switches, set a unique address. Set the Tens (10's) switch to the tens digit of the address,
2
and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
0
10's
0
1's
NOTE The Unit Vent recognizes its address only after power has been cycled.
Set communications selector for BACnet ARC156.
3
Set the both DIP switches 3 and 4 OFF for BACnet ARC156.
4
NOTE The baud rate for BACnet ARC156 is automatically 156 kbps, so DIP switches 1 and 2 are overridden.
Connect the communications wiring to the Comm port in the screw terminals labeled Net +, Net -, and Shield.
5
Wire specifications
A dedicated 22 AWG shielded twisted pair wire (EIA 485)
○
Maximum wire length 2000 feet (610 meters) or 32 nodes
○
Devices should be daisy-chained and not star-wired
○
Attach the drain/shield wire to both ends of the network segment and through every controller
○
NOTE Use the same polarity throughout the network segment.
Turn on the power for the Unit Vent by connecting power terminals.
6
Unit Ventilator
Integration Guide
8