Enertech Bentone B2S Classic Installation And Maintenance Instruction

Advertisement

Quick Links

178 017 32
Providing sustainable energy solutions worldwide
Installation- and maintenance instruction
B2S Classic

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Bentone B2S Classic and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Enertech Bentone B2S Classic

  • Page 1 178 017 32 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B2S Classic...
  • Page 3: Table Of Contents

    Contents 01. GENERAL ........................... 5 Description .................................. 5 Declaration of conformity ............................6 Safety directions ................................ 7 02. TECHNICAL DATA ........................8 Type designation B2 ..............................8 Dimensions ................................. 8 Burner capacity ................................8 Recommended nozzle ..............................8 Table of nozzles ................................8 03.
  • Page 5: General

    01. GENERAL Description 1. Shrouded disc 2. Preheater 3. Photoresistor 4. Electric contact X1,X2 (see wiring diagram) 5. Air damper 6. Oil pipe 7. Electrodes 8. Fan housing 9. Adjustment of nozzle assembly 10. Frame 11. Control box 12. Blast tube 13.
  • Page 6: Declaration Of Conformity

    B 9, B 10, B 11 13129815007 B 45 MF, B 45-2 MF Enertech AB försäkrar under eget ansvar att ovannämnda produkter är Enertech AB erklärt in eigener Verantwortung, dass obenstehende Produkte mit folgenden Normen oder anderen normativen Dokumenten i överensstämmelse med följande standarder eller andra regelgivande und anwendbare Teile in EU-Direktiven in Übereinstimmung stehen...
  • Page 7: Safety Directions

    01. GENERAL - The contents of this manual are to be observed by all who work for any reason on the unit and its appertaining system parts. - This manual is intended especially for authorised personnel. - This manual is to be regarded as part of the burner and shall always be available near the place of installation.
  • Page 8: Technical Data

    02. TECHNICAL DATA Type designation B2 Model S Dimensions ø89,5 Length of Projecting from blast tube flange, size B 130-150 Burner capacity 3,1-8,2 kg/h 37,0-97,0 kW -0,5 Burner output kW Recommended nozzle Both 60° and 80° and both types S and H can be used. Which nozzle type gives the best result depends on the shape of the combustion chamber.
  • Page 9: Installation

    03. INSTALLATION Acceptance inspection Ensure that everything is delivered and that there is no transport damage. If there is anything wrong with the delivery, please report it to the supplier. Any transport damage should be reported to the forwarding company. Preparations for installation Ensure that the size and capacity range of the burner are suitable for the boiler.
  • Page 10: Basic Settings

    04. BASIC SETTINGS Nozzle 1,75gph 0,75gph 1,00gph 1,25gph 1,50gph Burner output without preheater 2,00gph Burner output, kW Adjustment of the nozzle assembly Burner output, kW Air adjustment Burner output, kW Pressure in front of the shrouded disc Burner output, kW 171 725 06 06-01...
  • Page 11: Maintenance

    05. MAINTENANCE Suspension of burner During service the burner can be hung up on the screw in the burner flange. For this there is a hole on the right side of the burner.The blast tube, shrouded disc, nozzle and electrodes are then easily accessible. Removing the blast tube 1.
  • Page 12: Cleaning The Fan Wheel

    05. MAINTENANCE Cleaning the fan wheel The outer fan housing half is kept firm by 5 screws. Trimming If the size of the nozzle is changed, it is suitable to first set the nozzle assembly and air according to the recommendations in section Basic settings. For the individual boiler installation, adjustments can then always be made to optimise economy, operational reliability and environmental effects.
  • Page 13: Service Position Electric Package

    05. MAINTENANCE Service position electric package Loosen the hexagon nut from the stud bolt. Pull the electric package backwards and rotate it ca. 90° clockwise. When required the electric package can be suspended in the cables. Pump filter When changing pump filter, see chapter 06. 171 755 19 05-01...
  • Page 14: Instructions Pump Type Bfp 41L3

    06. INSTRUCTIONS PUMP TYPE BFP 41L3 Technical data Viscosity range: 1,3-12,0 mm Pressure range: 7-15 bar Oil temperature: -10 to+70°C Components 1. Nozzle connection G 1/8" 2. Pressure gauge connection G 1/8" 3. Pressure control 4 mm Allen key 4. Cartridge filter 5.
  • Page 15: Bfp 41L3 Operating Principle

    06. INSTRUCTIONS PUMP TYPE BFP 41L3 BFP 41L3 operating principle When the pump is started, oil is drawn from the suction port (S) through the filter (H) to the suction port (C) of the gear-set. The oil then moves to the pressure side of the gearwheel and is thus press- urised.
  • Page 16: Suction Line Tables

    06. INSTRUCTIONS PUMP TYPE BFP 41L3 Suction line tables One-pipe system One-pipe system Height Pipe diameter Height Pipe diameter ø4 mm ø5 mm ø6 mm ø4 mm ø5 mm ø6 mm With an underlying tank a one-pipe system is not recommended Two-pipe system Two-pipe system Height...
  • Page 17: Oil Filter Bentone

    07. OIL FILTER BENTONE We recommend the use of a fine filter in front of the oil burner. For certain markets this is delivered enclosed in the carton. Specification Oil filter for light oil with disposable filter cartridge Connection: 1/4" Filter grade: 20 µm Water repellent Filter area: 0.17 m...
  • Page 18: Electrical Equipment Loa24

    09. ELECTRICAL EQUIPMENT LOA24... Wiring diagram (1)(2) 1(2) 171 855 18 04-01...
  • Page 19: List Of Components

    09. ELECTRICAL EQUIPMENT LOA24... List of components Oil burner control Photoresistor Twin thermostat Main switch Fuse, max. 10A Ignition transformer Alarm lamp Solenoid valve Signal lamp (optional) Plug-in contact, burner M1 Burner motor Plug-in contact, boiler Time meter (optional) Mains connection and fuses in accor-dance with local regulations. Function 1.
  • Page 20: Fault Location

    10. FAULT LOCATION Burner fails to start Possible causes Situation Remedies Motor runs Flame instability Check nozzle to burner head dimension and Burner pre-purges Incorrect head settings electrode position Check oil pressure Low oil pressure Adjust air damper Excess air Flame occurs Burner locks out Photocell not seeing light...
  • Page 21 OIL BURNERS MAINTENANCE INSTRUCTIONS General information If the burner starts but does not ignite Keep the boiler room clean. Ensure that the boiler Make an attempt to start the burner. room has permanent fresh air intake. Switch off before Never make close repeated start attempts. dismantling the oil burner.
  • Page 24 Enertech AB. P.O Box 309, SE-341 26 Ljungby. www.bentone.se, www.bentone.com...