Section 4 Dnp3 Parameters; Parameter List - ABB RELION Series Communication Protocol Manual

Grid automation dnp3 communication protocol manual
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758757 A
Section 4
4.1
Table 4:
DNP3 settings
Parameter
Values (Range)
Operation
Port
Unit address
Master address
Mapping select
ClientIP
TCP port
TCP write authority
Link keep-alive
Validate master addr
Self address
Need time interval
Table continues on next page
REC615 and RER615
Communication Protocol Manual
DNP3 parameters

Parameter list

The DNP3 parameters can be accessed with PCM600 or via the LHMI path
Configuration/Communication/DNP3.0n.
Some parameters are not visible in the "Basic" setting visibility mode.
To view all parameters use "Advanced" setting visibility mode in
Parameter Setting tool in PCM600 and LHMI.
Power must be cycled to the unit after making changes to the DNP3
parameters. The LHMI or WHMI do not notify that this action must be
taken.
Unit
1=on
5=off
1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet TCP
+UDP 1
1...65519
1...65519
1...2
20000...65535
0=No clients
1=Reg. clients
2=All clients
0...65535
s
1=Disable
2=Enable
1=Disable
2=Enable
0...65535
min
Step
Default
5=off
3=Ethernet - TCP
1
1
1
1
3
1
1
0.0.0.0
1
20000
2=All clients
1
0
1=Disable
2=Enable
1
30
Section 4
DNP3 parameters
Description
Operation Off / On
Communication interface selection
DNP unit address
DNP master and UR address
Mapping select
IP address of client
TCP Port used on ethernet
communication
0=no client controls allowed; 1=Controls
allowed by registered clients; 2=Controls
allowed by all clients
Link keep-alive interval for DNP
Validate master address on receive
Support self address query function
Period to set IIN need time bit
27