WEG UR11 Series User Manual page 36

Rectifier unit
Table of Contents

Advertisement

XC2
1
NO1
RL1 digital output with DC bus OK function (UDC1 &
UDC2 OK).
2
C1
- UDC1: DC bus of the rectifier bridge 1.
3
NC1
- UDC2: DC bus of the rectifier bridge 2.
4
NO2
RL2 digital output with no temperature alarm function.
5
C2
6
NC2
7
NO3
RL3 digital output with no temperature fault function.
8
C3
9
NC3
The RL1, RL2 and RL3 relay digital outputs of the CIR11 board
the operation status of the UR11 and the alarm and fault conditions of the temperature. The NO position
indicates that the UR11 is under regular operation and the NC position indicates a fault/alarm situation. Refer
to
section 5.2 FAULTS, ALARMS, AND POSSIBLE CAUSES on page 5-1
XC101
XC102
XC3T
XC3S
XC3R
DIP
SWITCH S1
The XC3R, XC3S, XC3T connectors located in the CIR11 board receive the NTCs signals that monitor the
heatsink temperatures.
The CIR11 board sets the rated operation voltage of the UR11 through the DIP switch S1. The 400 V model
(UR111140T4SZ) can be set to four different voltage levels: 380 V, 400 V / 415 V, 440 V / 460 V and 480 V
(refer to
Table 3.10 on page
DIP Switch
S1:1
S1:2
OFF
OFF
OFF*
ON*
ON
OFF
ON
ON
* Factory default setting.
Table 3.9 - XC2 Connector signals of the CIR11
Standard Function
XC1
Figure 3.20 - CIR11 board connection points
3-19).
Table 3.10 - Configuration of the DIP switch S1
UR111140T4 (Line 400 V)
480 V
440 V / 460 V*
400 V / 415 V
380 V
Installation and Connection
Specifications
Contacts rating: 1 A.
Maximum voltage: 240 Vac.
NC - normally closed contact.
C - common.
NO - normally open contact.
(Figure 3.20 on page
for more details.
XC2
CIR11 board
(status LEDs)
Rated Voltage
UR110893T5 (Line 500 V)
600 V
550 V / 575 V*
500 V / 525 V
3-19) are used to monitor
UR110811T6 (Line 690 V)
660 V / 690 V*
UR11 | 3-19
3