M-system R7G4FML3-6-DC16A Instruction Manual page 8

Npn transistor output module
Table of Contents

Advertisement

• Input /Output Data Details
Input Data: Slave stations -> master station readback value is set.
CH0 IN LO
CH0 Data Low order 8 bits
CH0 IN HI
CH0 Data High order 8 bits
CH1 IN LO
CH1 Data Low order 8 bits
CH1 IN HI
CH1 Data High order 8 bits
CH2 IN LO
CH2 Data Low order 8 bits
CH2 IN HI
CH2 Data High order 8 bits
CH3 IN LO
CH3 Data Low order 8 bits
CH3 IN HI
CH3 Data High order 8 bits
Output Data: Master station -> slave stations data is set.
CH0 OUT LO
CH0 Data Low order 8 bits
CH0 OUT HI
CH0 Data High order 8 bits
CH1 OUT LO
CH1 Data Low order 8 bits
CH1 OUT HI
CH1 Data High order 8 bits
CH2 OUT LO
CH2 Data Low order 8 bits
CH2 OUT HI
CH2 Data High order 8 bits
CH3 OUT LO
CH3 Data Low order 8 bits
CH3 OUT HI
CH3 Data High order 8 bits
CMD_CTRL
CMD_CTRL command area is following.
BIT
FUNCTION
0 - 2
Reserve
3
ALM_CLR
4 - 5
Reserve
6 - 7
CMD_ID
8 - 15
Reserve
CMD_STAT
CMD_STAT response area is following.
BIT
FUNCTION
0
D_ALM
1
D_WAR
2
CMDRDY
3
ALM_CLR_CMP
4 - 5
Reserve
6 - 7
RCMD_ID
8 - 11
CMD_ALM
12 - 15
COMM_ALM
Output data readback data bits 0 - 7 are set.
Output data readback data bits 8 - 15 are set.
Not in use
Not in use
Not in use
Not in use
Not in use
Not in use
Output data bits 0 - 7 are set.
Output data bits 8 - 15 are set.
Not in use
Not in use
Not in use
Not in use
Not in use
Not in use
REMARKS
Not used
0: Clear alarm/warning disabled
1: Clear alarm/warning triggered
Not used
Not used in the standard I/O command profile
Not used
REMARKS
Not used
Not used
1: Command reception enabled
0: Other
1: Completion of execution of ALM_CLR
0: Other
ALM_CLR_CMP can be cancelled by setting "0" for CMD_CTRL.ALM_CLR.
Not used
Not used in the standard I/O command profile
Warning
0: Normal, 1: Invalid data
Alarm
8: Unsupported command received, 9: Invalid data, A: Command ex-
ecution condition error, B: Subcommand combination error, C: Phase
error
Warning
0: Normal, 1: FCS error, 2: Command data not received, 3: Synchro-
nous frame not received
Alarm
8: FCS error, 9: Command data not received, A: Synchronous frame
not received, B: Synchronization time interval error, C: WDT error
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R7G4FML3-6-DC16A
EM-7774-B Rev.2
P. 8 / 10