M-system R7G4FML3-6-DC16A Instruction Manual page 6

Npn transistor output module
Table of Contents

Advertisement

• ID_RD (03H)
Reads the product ID.
BYTE
COMMAND
0
ID_RD (03H)
1
00H
2
CMD_CTRL
3
4
ID_CODE
5
OFFSET
6
SIZE
7
≥ 8
00H
• CONFIG (04H)
No parameter to set for this unit. Immediately response with completion.
BYTE
COMMAND
0
CONFIG (04H)
1
00H
2
CMD_CTRL
3
4
00H
≥ 5
00H
• ALM_RD (05H)
Reads alarm or warning
BYTE
COMMAND
0
ALM_RD (05H)
1
00H
2
CMD_CTRL
3
4
0000H
5
6
0000H
7
≥ 8
00H
• ALM_CLR (06H)
Clears alarm or warning
BYTE
COMMAND
0
ALM_CLR (06H)
1
00H
2
CMD_CTRL
3
4
0000H
5
≥ 6
00H
RESPONSE
ID_RD (03H)
00H
CMD_STAT
ID_CODE
OFFSET
SIZE
ID
RESPONSE
CONFIG (04H)
00H
CMD_STAT
00H
00H
RESPONSE
ALM_RD (05H)
00H
CMD_STAT
0000H
0000H
00H
RESPONSE
ALM_CLR (06H)
00H
CMD_STAT
0000H
00H
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
REMARKS
Read ID command
Not used
Refer to CMD_CTRL/CMD_STAT.
Refer to ID_CODE
OFFSET: designates the place to read data
SIZE: specify the size of data to read
Product's ID
REMARKS
Setup device command
Not used
Refer to CMD_CTRL/CMD_STAT.
Recalculation of parameters and set up. Other than 00H
is not supported.
Reserve
REMARKS
Read alarm or warning command
Not used
Refer to CMD_CTRL/CMD_STAT.
Read current alarm or warning.
12 points max. (2 bytes in 8th to 31st byte)
Other than 00H is not available.
0
0
REMARKS
Clear alarm or warning command
Not used
Refer to CMD_CTRL/CMD_STAT.
Clear current alarm or warning. Other than 00H is not
available.
Reserve
R7G4FML3-6-DC16A
EM-7774-B Rev.2
P. 6 / 10

Advertisement

Table of Contents
loading