DIP■switches■settings■
The DIP switches are accessed by removing the transparent cover.
1, 2:
Control signal Type
3, 4, 5:
Control signal Ranges
6: Action
7: Electrical Manual Override 7
8: Control signal failure
position preset*
* Does not operate with mA control.
(Proportional models only)
1
1
VDC
2
2
3
0...10
VDC
4
3
0...5 VDC
4
3
5...10
VDC
4
3
Free
Range
4
5
---
5
6
DA
6
OFF
7
8
8
Up
PB_VA-7700_Electricl Valve Actuators_02 2011
Default■setting■from■factory:
mA
All switches in left hand position
---
---
0...20 mA
4...20 mA
RA
ON
Down
1.
Voltage control
2.
3.
0...10 VDC
4.
5. ---
6. Direct Acting mode
7. Electrical manual override "off"
8. "Signal failure position" pre-set = "Up"
5