Applications - Siemens SIRIUS 3RU Manual

Industrial controls, protection devices, thermal/electronic overload relays
Hide thumbs Also See for SIRIUS 3RU:
Table of Contents

Advertisement

3.3

Applications

Table 3- 4
Applications
System protection
Motor protection
Alternating current, 3-phase
Alternating current, 1-phase
DC current
In the main circuit, the devices provide overload protection for the assigned electrical loads (e.g.
1)
motors), feeder cable, and other switching and protection devices in the respective load feeder.
The 3 phases have to be under symmetrical load.
3RU21 thermal overload relays
3RU21 thermal overload relays have been designed to protect three-phase loads, DC loads,
and single-phase AC loads.
Note
Protection of DC loads/single-phase AC loads
If a 3RU21 thermal overload relay is to be used to protect DC loads or single-phase AC
loads, all the bimetal strips have to be heated. Therefore, all of the relay's main current paths
have to be connected in series.
3RB20 / 3RB21 and 3RB30 / 3RB31 electronic overload relays
3RB20 / 3RB21 and 3RB30 / 3RB31 electronic overload relays are designed to protect
three-phase loads in sinusoidal 50/60 Hz voltage supplies.
Note
DC loads/Single-phase AC loads
The relay is not suitable for protecting DC loads or single-phase AC loads. On single-pole
loads, the 3RU21 thermal overload relay or the 3RB22, 3RB23 and 3RB24 electronic
overload relays for higher applications (no protection for DC loads) must be used for IO-Link.
Reference
More information ...
About overload relay applications
SIRIUS 3RU thermal overload relays / SIRIUS 3RB electronic overload relays
Manual, 09/2016, A5E03656507420A/RS-AB/003
Overview of applications
3RU21
3RB20 / 3RB21
3RB30 / 3RB31
1)
Can be found in the chapter titled ...
Configuration (Page 59)
Product description
3.3 Applications
1)
-
-
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rb

Table of Contents