Download Print this page

Operation; Maintenance - Cooper Lighting Sure Lites EBP1400NCX Instruction Manual

Advertisement

EBP1400NCX and EBP1400NCF Instruction Manual
Lamp Compatibility Table
Lamp Type
T5
T5
T5HO
T5HO
T5 CIR
T8
T8
T8U
T9 CIR
T12
T12
T12HO
T12HO
T12VHO
BIAX

OPERATION

When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When
power fails, the emergency ballast automatically switches to emergency power, operating one lamp at reduced
illumination for at least 90 minutes.

MAINTENANCE

Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically
to comply with local codes. The following schedule is recommended:
1. Visually inspect the charging light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds. Depending on
installation, one lamp should operate at reduced illumination.
3. Conduct a 90 – minute discharge test once a year. Depending on installation, one lamp should operate at reduced
illumination for at least 90 minutes.
Refer any service requirements indicated by these checks to qualified personnel.
NOTE: After installing the test button / indicator light, mark it with the appropriate label.
4
COOPER LIGHTING SOLUTIONS
Number
of Lamps
Low/High (Red) Output
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ADX142715
Installation instructions
Lamps Connected to
HIGH (RED)
"LOW (RED / WHITE)"
HIGH (RED)
"LOW (RED / WHITE)"
HIGH (RED)
HIGH (RED)
"LOW (RED / WHITE)"
HIGH (RED)
HIGH (RED)
HIGH (RED)
"LOW (RED / WHITE)"
HIGH (RED)
"LOW (RED / WHITE)"
"LOW (RED / WHITE)"
HIGH (RED)
Wattage
6 - 25, 39
28 - 35
24
54 - 80
22 - 55
15 - 32
59 - 86
32
20 - 32
20 - 75
75 - 95
35
95 - 110
215
18 - 55

Advertisement

loading

This manual is also suitable for:

Sure lites ebp1400nc