Download Print this page
Cooper Lighting Sure Lites EBP1400NCX Instruction Manual

Cooper Lighting Sure Lites EBP1400NCX Instruction Manual

Advertisement

Quick Links

ADX142715
EBP1400NCX and EBP1400NCF Instruction Manual
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
EBP1400NCX
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
OBSERVED INCLUDING THE FOLLOWING.
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and
at heights where it will not readily be subject to
tampering by unauthorized personnel.
5. The use of accessory equipment not recommended
by Sure-Lites may cause an unsafe condition.
6. Do not use this equipment for other than its
intended purpose.
7. SAVE THESE INSTRUCTIONS
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before
installing or servicing.
EBP1400NCF
NOTES:
Note 1. To prevent high voltage from being present on
the output terminals (red/white, red, and yellow), do
not connect the test button indicator light to the EBP
until Step 7 of the installation instructions.
Note 2. This product is for use with most 2' through
8' (6W-215W single and bi-pin fluorescent lamps
including energy saving, circline, U-shaped and biax.
For specific lamp compatibility, please see the table
later in the instructions.
Note 3. Make sure all of the connections are in
accordance with the National Electrical Code and any
local regulations.
Note 4. To reduce the risk of electrical shock,
disconnect both normal and emergency power
supplies and the test button indicator light (which
disconnects the battery) before servicing.
Note 5. This emergency ballast is for factory or field
installation in the ballast channel.
Note 6. This product is for use in indoor fixtures. This
product is not intended for use near air handling
heated air outlets or in wet or hazardous locations.
Note 7. An unswitched AC power source is required
(120, 240, or 277 volts).
Note 8. Do not attempt to service the battery. A sealed,
no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information
on service.
Note 9. Servicing should be performed by qualified
service personnel.
Brand Logo
reversed out of
black
INS #
INS #
WARNING
For use in temperature rating
20°C to 55°C
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
Ni - Cd

Advertisement

loading

Summary of Contents for Cooper Lighting Sure Lites EBP1400NCX

  • Page 1 Brand Logo reversed out of black ADX142715 INS # INS # EBP1400NCX and EBP1400NCF Instruction Manual WARNING WARNING Risk of Fire/Electric Shock Risk of Electric Shock If not qualified, consult an electrician. Disconnect power at fuse or circuit breaker before installing or servicing.
  • Page 2: Installation

    9. A short term discharge test may be conducted after EBP1400NCX only the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long – term discharge test. Refer to OPERATION. COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 3 Emergency Ballast Leads to Test Button/ Ballast Channel Indicator Light Cover Test Button/ Indicator Light 7/8" Punch 7/8" Bushing Inserted into Plastic Tubing Ballast Channel (cut to necessary Cover length) Test Button/ Indicator Light COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 4: Operation

    3. Conduct a 90 – minute discharge test once a year. Depending on installation, one lamp should operate at reduced illumination for at least 90 minutes. Refer any service requirements indicated by these checks to qualified personnel. NOTE: After installing the test button / indicator light, mark it with the appropriate label. COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 5 EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 6 EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 7 EBP1400NCX and EBP1400NCF Instruction Manual WIRING DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLAST. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS COOPER LIGHTING SOLUTIONS ADX142715 Installation instructions...
  • Page 8 When using the auxillary relay to switch the neutral line, the Emergency and A.C. ballasts must be on the same branch circuit. Warranties and Limitation of Liability Please refer to www.cooperlighting.com for our terms and conditions. Cooper Lighting Solutions is a registered trademark. All trademarks are property © 2020 Cooper Lighting Solutions of their respective owners.

This manual is also suitable for: