Design Features; Compressor Construction; Compressor Cooling; Lubrication - Emerson Copeland 4MTL-05 Application Manuallines

Stream co2 semi-hermetic compressors for transcritical & subcritical applications
Hide thumbs Also See for Copeland 4MTL-05:
Table of Contents

Advertisement

discharge shut-off valve) the temperature is expected to be 15-20 K lower than inside the cylinder
head. This fact must be taken into account when applying the values in Table 4 below.
Application
Low temp
Medium temp
Compressors in parallel
or multi-compressors
Table 4: Superheat recommendations
Attention! The values shown in Table 4 are maximum temperature values inside the cylinder head.
When using a discharge temperature sensor on the discharge line, the temperature drop has to be
considered for the high DLT cut-out setpoint.
NOTE: An additional internal heat exchanger might be required to ensure the recommended
suction superheat values on the compressor inlet are achieved.
2.5

Design features

2.5.1 Compressor construction

Stream CO
compressors have a large discharge chamber to eliminate pulsations. The cylinder
2
heads and the discharge plenum are designed to minimize the heat transfer to suction side.
Each cylinder head has a plugged 1/8" - 27 NPTF tapped hole on the high pressure.
Figure 6: Compressor external view

2.5.2 Compressor cooling

Compressor motor cooling must be ensured in all circumstances.
All Stream CO
compressors are suction gas-cooled. With suction gas-cooled compressors, the
2
motor is cooled by refrigerant gas that is led through / over the motor. Depending upon the operating
conditions, the maximum allowed suction gas superheat shall not exceed the values shown in the
envelopes.

2.5.3 Lubrication

For small- and medium-size Stream CO
30), an oil splasher system ensures proper lubrication at constant or variable speed.
For large models (4MTL-35 to 4MTL-50) an oil pump is used:
▪ On compressors with Next Generation CoreSense™ (-N) or formerly delivered with CoreSense™
Diagnostics (-D), the oil pump integrates an electronic switch to ensure the oil pressure safety
functionality.
▪ Compressors with CoreSense™ Protection (-P) are designed to accommodate fittings for an
OPS2 or a standard oil pressure switch (OPS2 oil sensor included in the oil pump).
▪ The oil pumps used on these compressors are independent of their rotating direction.
AGL_Stream_ST_4MTL_4MSL_E_Rev01
Minimum
Minimum oil
superheat
temperature
required
required
20 K / 36 °F
30 °C / 86 °F
10 K / 18 °F
30 °C / 86 °F
10 K / 18 °F
30 °C / 86 °F
compressors (4MSL-03 to 4MSL-15, 4MTL-05 to 4MTL-
2
Maximum acceptable discharge
temperature
Stream
154.4 °C / 310 °F 121.1 °C / 250 °F
154.4 °C / 310 °F
154.4 °C / 310 °F
Scroll
N/A
N/A
7