Screens - Emerson Copeland 4MTL-05 Application Manuallines

Stream co2 semi-hermetic compressors for transcritical & subcritical applications
Hide thumbs Also See for Copeland 4MTL-05:
Table of Contents

Advertisement

Compressor
Transcritical Subcritical
4MTL-05
4MSL-03
4MTL-07
4MSL-04
4MTL-09
4MSL-06
4MTL-12
4MSL-08
4MTL-15
4MSL-12
4MTL-30
4MSL-15
4MTL-35
---
4MTL-40
---
4MTL-50
---
Table 10: Variations with smaller tube connections
3.4

Screens

CAUTION
Screen blocking! Compressor breakdown! Use screens with at least
0.6 mm openings.
The use of screens finer than 30 x 30 meshes (0.6 mm openings) anywhere in the system should be
avoided with these compressors. Field experience has shown that finer mesh screens used to protect
thermal expansion valves, capillary tubes or accumulators can become temporarily or permanently
plugged with normal system debris and block the flow of either oil or refrigerant to the compressor.
Such blockage can result in compressor failure.
AGL_Stream_ST_4MTL_4MSL_E_Rev01
Flange
Displ.
Mountings
Inner Ø
(m³/h)
(mm)
brazing
4.60
6.20
45 x 45
7.40
9.54
12.50
52 x 52
17.90
22.70
70 x 70
26.80
&
52 x 52
32.00
Variation smaller Ø
Suction connection
Valve
description
W17.2 /
1/2"
ODS 1/2
W22 /
5/8"
ODS 5/8
W35 /
1
"
ODS 1
"
Discharge connection
Inner Ø
Valve
brazing
description
W17.2 /
1/2"
ODS 1/2
W17.2 /
1/2"
ODS 1/2
W30 /
7/8"
ODS 7/8
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents