Wiring Work (Continued)
16
E-
NASA_Floor Stand_AM@@@FNFDEH@_IM_EN_03678A-05.indd 16
Select the power cable in accordance with relevant local and national
regulations.
Wire size must comply with local and national code.
Power Supply cords of parts of appliances for outdoor use shall not be lighter
than polychloroprene sheathed flexible cord.(Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
You should connect the power cable into the power cable terminal
and fasten it with a clamp.
The unbalanced power must be maintained within 10% of supply
rating among whole indoor units.
If the power is unbalanced greatly, it may shorten the life of the
condenser. If the unbalanced power is exceeded over 10% of
supply rating, the indoor unit is protected, stopped and the error
mode indicates.
To protect the product from water and possible shock, you should
keep the power cable and the connection cord of the indoor and out-
door units in the iron pipe.
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated
in the fixed wiring(≥3mm).
You must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and
communication cable.
Maximum length of power cables are decided within 10% of power
drop. If it exceeds, you must consider another power supplying
method.
The circuit breaker(ELCB or MCCB+ELB) should be considered more
capacity if many indoor units are connected from one breaker.
Use round pressure terminal for connections to the power terminal
block.
For wiring, use the designated power cable and connect it firmly,
then secure to prevent outside pressure being exerted on the
terminal board.
Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make
proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal screws.
Tightening torque
kgf
cm
N
m
M3.5
8.0~12.0
0.8~1.2
M4
12.0~18.0
1.2~1.8