Honeywell 7800 Series Installation Instructions Manual page 21

Valve proving primary relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

Table 9. Blinking Fault Codes and Recommended Troubleshooting. (Continued)
Blink Code
System Failure
Code 2-3
Flame signal value is
*Flame Signal
too high to be valid.
Overrange*
Code 3-1
Running or Lockout
*Running/Inte
Interlock fault during
rlock Switch
Pre-Purge.
Problem*
Code 3-2
Lockout Interlock
*Running/Inte
powered at improper
rlock On
point in sequence or
During
On in Standby.
Standby*
Code 3-3
VPS (Valve Proving
*VPS in
Switch) in wrong state
Improper
during VPS Test.
State*
Code 4-1
No purge card or the
*Purge Card
purge card timing has
Problem*
changed from the
original configuration.
Code 4-2
Pilot (ignition) valve
*Wiring
terminal, main valve,
Problem/Inter
ignition or Main Valve
nal Fault*
2 was on when it
should be off.
RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
Recommended Troubleshooting
1. Make sure the flame detector and flame amplifier are compatible.
2. Remove the flame amplifier and inspect its connections. Reset the flame
amplifier.
3. Reset and sequence the Relay Module.
4. Check the flame detector sighting position; reset and recycle. Measure
flame strength. Verify that it meets specifications. If not, refer to the flame
detector and/or flame amplifier checkout procedures in the installation
instructions.
5. If the code reappears, replace the flame amplifier and/or the flame detec-
tor.
6. If the fault persists, replace the Relay Module.
1. Check wiring; correct any errors.
2. Inspect the fan; make sure there is no air intake blockage and that it is
supplying air.
3. Make sure the Lockout Interlock switches are functioning properly and
the contacts are free from contaminants.
4. Reset and sequence the Relay Module to Pre-Purge (place the TEST/RUN
Switch in the TEST position, if available). Measure the voltage between
terminal 7 and G (ground); 120 Vac should be present. Switch TEST/RUN
back to RUN.
5. If steps 1 through 4 are correct and the fault persists, replace the Relay
Module.
1. Check wiring to make sure that the Lockout Interlocks are connected
properly between terminals 6 and 7. Correct any errors.
2. Reset and sequence the Relay Module.
3. If the fault persists, measure the voltage between terminal 6 and G
(ground), then between terminal 7 and G. If there is 120 Vac at terminal 6
when the controller is off, the controller switch may be bad or is jumpered.
4. If steps 1 through 3 are correct and there is 120 Vac at terminal 7 when
the controller is closed and the fault persists, check for a welded or
jumpered Running Interlock or Airflow Switch. Correct any errors.
5. If steps 1 through 4 are correct and the fault persists, replace the Relay
Module.
1. Check wiring, making sure upstream valve is connected to terminal 9 and
downstream valve is connected to terminal 17.
2. Conduct Valve Seat leakage test using a manometer.
3. Reset and sequence the Relay Module; if fault repeats, test VPS (con-
nected to terminal 16) is functioning properly; replace if necessary.
4. Reset and sequence the Relay Module.
5. If fault persists, replace the Relay Module.
1. Make sure the purge card is seated properly.
2. Inspect the purge card and the connector on the Relay Module for any
damage or contaminants.
3. Reset and sequence the Relay Module.
4. If the fault code reappears, replace the purge card.
5. Reset and sequence the Relay Module.
6. If the fault code persists, replace the Relay Module.
WARNING
Electrical Shock Hazard; Fire or Explosion Hazard.
Can cause severe injury, death or property damage.
Remove system power and turn off power supply.
1. Remove system power and turn off fuel supply.
2. Check wiring; correct any errors.
3. inspect Pilot Fuel Valve(s), both places, and connections.
4. Reset and sequence the Relay Module.
5. If the fault persists, replace the Relay Module.
21
32-00209—03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents