Transducers With Non-Amplified Analog Output; Standard Installation; Electrical Connections (Series M / W / K / I) - gefran MD Series Manual Of Electrical Installation

Pressure probes
Table of Contents

Advertisement

Transducers: Series M / Series W / Series K / Series I / TPS / TPF / TPH
Output: mV/V
Installation notes
- The transducer must be grounded (normally through the machine body or equipment it is installed on).
- Use a shielded cable only. The braiding on connector side must be left floating. The braiding on instrument / PLC side must be
connected to the power supply GND.
- To prevent interference, separate the power cables from the signal cables
Machine
Press
Equipment
Ground
Series M / W / K / I
mV/V output
6

4. Transducers with non-amplified analog output

Standard installation (recommended)
Rod / Pressure intake
Cable connector
Electrical connections
R-Cal
6-pin connector
VPT07RA10-6PT2
(PT02A-10-6P)
Floating braiding (not connected)
Shielded cable
6-pin
+
Power supply
C
-
Power supply
D
-
Signal
B
+
A
Signal
Calibration shunt
E - F
n.c.
Connect the cable sheathing
to the side of the instrument
8-pin connector
PC02E-12-8P Bendix
MAN_Electrical_Installation_for_Pressure_Probes_0709_ENG
PLC / Instrument
8-pin
A
C
D
B
E - F
G - H