Operation; Programming; Measuring Units; K Factor (Pulses Per Unit) - Tecfluid CIP Series Instruction Manual

Table of Contents

Advertisement

4

OPERATION

To adapt the converter to the meter, the pulses per unit factor specified on the meter must
be programmed. To do this, the plastic front cover must be removed by unscrewing the four
screws on the corners. After that, the push buttons will be accessible.
There are three push buttons with the following functions:
4.1

Programming

By pushing the two push buttons PROG at the same time for at least two seconds, the
display will change to the first stage of the programming mode.
4.1.1

Measuring Units

In this screen the measuring units can be programmed.
There are seven options of units: pounds (lb), cubic metres (m
(L), kilograms (kg), grams (g), and without specific units selected (all units off). The selected
unit will be flashing on the display (except when no specific units are selected). Use the push
button marked with the arrow pointing upwards to change from one unit to the next. By
pushing the two push buttons PROG at the same time (do not keep the push buttons
pushed) the selected unit will be saved into memory and the next programming screen for
the k factor will appear. If the RESET push button is pressed then the next programming
screen for the k factor will appear but the selected unit will not be saved into memory and
the previous measuring unit will be retained.
4.1.2

k factor (pulses per unit)

3
5
), U.S. Gallons (USGAL), litres