Tecfluid MT03L Series Instruction Manual

Electronic converter for level transmitters

Advertisement

Quick Links

Instructions manual
Series MT03L
Electronic converter for level transmitters
The art of measuring
R-MI-MT03L Rev.: 2 English version

Advertisement

Table of Contents
loading

Summary of Contents for Tecfluid MT03L Series

  • Page 1 Instructions manual Series MT03L Electronic converter for level transmitters The art of measuring R-MI-MT03L Rev.: 2 English version...
  • Page 2 PREFACE Thank you for choosing the MT03L converter from MT03 series of Tecfluid S.A. This instruction manual allows the installation, configuration and programming of the electronic converter MT03L. It is recommended to read it before using the equipment. WARNINGS • This document shall not be copied or disclosed in whole or in any part by any means, without the written permission of Tecfluid S.A.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS INTRODUCTION ................RECEPTION ................. Storage temperature ............INSTALLATION ................Location ................Electrical connection ............3.2.1 Power supply wiring ..........3.2.2 Resistance input wiring .......... 3.2.3 Current input wiring ..........3.2.4 Analog output wiring ..........3.2.5 Relay output wiring ..........OPERATION .................
  • Page 4 SERIAL NUMBER ................SOFTWARE VERSION ..............BRIGHTNESS ................WORKING SCREEN ..............MAINTENANCE ................12.1 Fuse .................. ASSOCIATED SOFTWARE WINSMETER MT03 ....... 13.1 USB cable connection and drivers installation ...... 13.2 Port connection ..............13.3 Access to installation and programming ....... 13.4 Visualization ...............
  • Page 5: Introduction

    INTRODUCTION MT03L converters are indicators for level measurement applications. The electronic circuit is based on the most advanced technology in digital signal processing, in order to obtain accurate and reliable measurements. The equipment provides the following features (depending on the model): •...
  • Page 6: Electrical Connection

    Electrical connection The connection of the equipment is via plug-in connectors, polarized to avoid mistakes when plugged in. The connectors have screw terminals, as per VDE standards, to accept cables with section of 1.5 mm The pictures of the connections in this manual are always looking at the equipment from the back.
  • Page 7: Resistance Input Wiring

    Before starting the wiring of the instrument, check that the supply voltage available is the same as marked on the label of the converter. Terminal Power supply AC Power supply DC Phase Neutral In case of DC power supply, the equipment is provided by a diode bridge that allows connecting it regardless of the polarity.
  • Page 8: Analog Output Wiring

    Terminal mA (positive, power supply for a passive device) mA input mA (negative, input from an active device) This input is compatible with any flow rate transmitter that provides a 4-20 mA output. The impedance is 120 Ω. The input has a protection in order to limit the voltage applied to the circuit.
  • Page 9: Relay Output Wiring

    Terminal mA (positive, active output) mA (negative, passive output) The analog output is galvanically isolated. It can be either active (which means that the receiving device must be passive) or passive (which means that the receiver must supply the power for the current loop). It is recommended to use a receptor with an input resistance of less than 700 Ω...
  • Page 10 Terminal Description Relay Normally open Relay 1 Normally closed Relay 1 Common Relay 1 Normally open Relay 2 Normally closed Relay 2 Common Relay 2 The relay outputs provide relays with potential free contacts (see characteristics on page 29). The status of the relay contacts corresponds to the relay at rest.
  • Page 11: Operation

    OPERATION The MT03L converters have a graphic LCD and a keyboard with 4 push buttons. The following figure shows the functionality of the converter keys. (Down / Left) To change to the digit on the left. Into the menu, to scroll down. (Up) To increase the digit.
  • Page 12: Main Menu

    MAIN MENU To access the main menu of the converter, press the key (Enter). The following screen appears: Number of menu items Selected item The "Installation" option allows the basic configuration of the instrument, as explained in Chapter 6 of this manual. The "Programming"...
  • Page 13 To change the access password of the programming menu, select "Programming" in the main menu and then "Password". When the "Password" option is selected, a screen that indicates the password status for this menu appears. Selecting “Activate”, the screen to enter the new password appears.
  • Page 14: Installation Parameters

    If the password needs to be changed or disabled, the procedure is the same. Once entered the "Password" menu, the following screen appears: If Change is selected, the equipment will ask for a password again. If Disable is selected, the following message will appear: INSTALLATION PARAMETERS Power on the electronic converter with the voltage indicated on the label.
  • Page 15: Language

    Language The language in which all the menus will be displayed can be chosen. Input In this screen the type of signal from the sensor connected to the MT03L can be chosen. Resistance input is compatible with level transmitters of series LE and transmitters LTE of series LT, as well as with other level transmitters based on resistance variation.
  • Page 16: Distance Adjustment

    To perform the capture options, set the level meter at the lower limit position (e.g. float in its lowest position) and select the "Capture inf." with the key “Enter”. The following confirmation screen appears. Selecting Yes, the device reads the input signal and sets the lower limit level. The same procedure can be done with the capture of top level, placing the level meter at the upper limit position.
  • Page 17: Programming Parameters

    If 4 mA is selected, pressing the key (Enter) toggles between 4, 8, 12, 16 and 20 mA, allowing to check the adjustment of the analog output. Finally, in the last row, the selected input type and a number that is related to the value of that input is shown.
  • Page 18: Language

    Language You can choose the language in which all the menus will be displayed. Units In this screen the units for the level indication can be chosen. Decimals In this screen the number of decimals for the level indication can be selected. To select the number of decimals it must be taken into account that the instrument has 5 digits for level rate indication.
  • Page 19: Damping

    Damping The MT03L converter has an adaptive filter (damping) to provide stable level and analog output readings in the presence of continuous level fluctuations. The configuration of this filter can be very useful in the cases where the level readings have some instability (due to for example waves in the tank).
  • Page 20: 7.5.1.2 No Action

    Example 1 If the activation point is programmed to 100 cm and the deactivation point is programmed to 90 cm, when the level is zero the output will be deactivated. When the level reaches a value of 100 cm the output will be activated until the level falls below 90 cm. Example 2 If we program an activation point of 90 cm and a deactivation point of 100 cm, when the level is zero the output will be activated.
  • Page 21: 7.5.2.1 Programming Of The 4-20 Ma Output

    7.5.2.1 Programming of the 4-20 mA output Level values equivalent to each current are entered directly. Programming a level value for 20 mA higher than the one for 4 mA, the loop current changes from 4 to 20 mA as the level increases. Otherwise, programming a level value for 20 mA lower than the one for 4 mA, the current loop will change from 20 to 4 mA as the level increases.
  • Page 22: Brightness

    BRIGHTNESS With this option the screen backlight can be adjusted. WORKING SCREEN When exiting the menu, the display shows the working screen, indicating the level value in the previously selected units. This screen shows the relay output status, if they are activated. An “A”...
  • Page 23 The USB connector is located at the rear side of the converter. Connect the USB cable at one end to the converter and at the other to the computer where the software is installed. Power on the electronic converter. Execute the program WinsmeterMT03 following the sequence Start – Programs – Tecfluid S.A. - WinsmeterMT03.
  • Page 24: Port Connection

    13.2 Port connection In the "Port" section, choose the appropriate port for the converter. This will appear with the name of the port followed by MT03L and its serial number. Then click "Open". Once the port is open, the button "Open" in the "Installation" and “Programming” sections activates.
  • Page 25 Once the password is written, press “Enter” or "Open", and the installation or programming tab will open. At the bottom of each section the text "Installation tab open" or "Programming tab open" will be displayed To enter the Installation window, just click the corresponding tab. In the installation window the parameters that adapts the converter to a sensor can be configured.
  • Page 26: Visualization

    Changing the parameters of this screen you can program the different functions of the equipment. As in the previous paragraph, to program this data to the MT03L converter, press the “Send” button. The message "Saving program" will appear for two seconds in the converter screen. The programming data will be stored in the memory of the converter.
  • Page 27: Firmware Updates

    13.5 Firmware updates New firmware updates can be published in the website. These updates contain improvements or bug fixes that make the equipment operates at best conditions. The updates can be downloaded from the following link of Tecfluid S.A. website www.tecfluid.com/download To update the equipment, go to menu “Firmware”...
  • Page 28 Once the file is selected, press the “Program” button. A message “Programming device” will appear. The process takes about 90 seconds, after which the message “Device programmed” will appear. From this moment, the converter MT03L already has the new version of Firmware.
  • Page 29: Technical Characteristics

    TECHNICAL CHARACTERISTICS Power supply 90 ... 265 VAC 50, 60 Hz 18 ... 36 VDC Power consumption: ≤ 5 VA Resistance input Range: 0 … 6500 Ω Resolution: 2 Ω Current input Range: 4 … 20 mA Resolution: 7 μA Analog output 4-20 mA.
  • Page 30: Dimensions

    DIMENSIONS Panel hole...
  • Page 31: Troubleshooting

    TROUBLESHOOTING Problem Probable cause Solution Check that the input type Incorrect input programmed in the menu matches the connection made (see page 15) The displayed level is 0 Connect the cable between the Cable disconnected level sensor and the MT03L The display is blank Blown fuse Change the fuse...
  • Page 32 WARRANTY Tecfluid S.A. guarantee all the products for a period of 24 months from their sale, against all faulty materials, manufacturing or performance. This warranty does not cover failures which might be imputed to misuse, use in an application different to that specified in the order, the result of service or modification carried out by personnel not authorized by Tecfluid S.A., wrong handling or accident.