5 USER GUIDE
Note 5: If the IP address is not set or its setting is cleared, for instance, by clearing the memory
at the time of OS loading, all the processes come to a stop except IP address setup, with
the LER LED on the FL.NET module glowing and the S10mini CPU unit indicator
showing the following error message:
When the main module IP address is not set: "FLNMIPNG"
When the submodule IP address is not set: "FLNSIPNG"
Note 6: Before performing self-node setup and remote node reception setup, be sure to set the
IP address for the FL.NET module. If you perform self-node setup and remote node
reception setup while leaving FL.NET module IP address setup incomplete, a timeout
error occurs so that the setup process does not end normally.
5.3.2 Module installation and switch setup
For the procedures for module installation and switch setup, see "3 FL.NET MODULE
INSTALLATION."
5.3.3 Tool connection procedure
For the tool connection procedure, See "5.5 Installing and Starting Up the System."
5.3.4 Tool startup procedure
For the tool startup procedure, See "5.5 Installing and Starting Up the System."