6-2 Precautions When Working with Batteries

6-2-1 If battery acid contacts skin or clothing, wash immediately with soap and water. If
acid enters eye, immediately flood eye with running cold water for at lease
20minutes and get medical attention immediately.
6-2-2 NEVER smoke or allow a spark or flame in vicinity of battery or engine.
6-2-3 Do not drop a metal tool on the battery. The resulting sparks or short-circuit on the
battery or other electrical part may cause an explosion.
6-2-4 Remove personal metal items such as rings, bracelets, necklaces, and watches
when working with a lead-acid battery.
A lead-acid battery produces a short-circuit current high enough to weld a ring or
the like to metal, causing a severe burn.
7

Appendices A

7-1 Dip Switch (at the left side of inverter)
S1
FREQ. (Hz)
ON
60
OFF
50
----
----
----
----
S1 ( FREQ. Hz ) – 50Hz/60Hz
S2 S3 (BAUD RATE ) – 2400 / 4800 / 9600 / 19200
S4 S5 (VOLTAGE OUTPUT ) – 100VAC/110VAC/115VAC/120VAC
When you set up S1~S5, please reset the inverter and let update data through CPU.
7-2 AC Output Voltage Tune (VR)
Tune VR ( VAC ) output voltage from 100 – 120 VAC or 200 – 240 VAC
The VAC value will gradually increase, tune VR from right to left.
S2
S3
BAUD RATE
ON
ON
OFF
ON
ON
OFF
OFF
OFF
S4
POWER SAVING
2400
ON
4800
OFF
9600
----
19200
----
16
ACV-ADJ
H--------L
DISABLE
240V 200V
H--------L
ENABLE
120V 100V
-----
-----
----
----