Trial Run Mode - LG AK-Q240BC01 Installation Manual

Single package type air conditioner
Table of Contents

Advertisement

INSTALLATION OF UNIT
28
To Increase Belt Tension
1
Loosen adjustment nut(4places).
2
Pull motor back until belt is tight.
3
Tighten adjustment bolt after belt has
correct tension.
FORCE(F)
HEIGHT(S)
2.5(kgf)
8~11mm
1.5(kgf)
7~9 mm

Trial Run Mode

After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
REMARK
B
A
F
S