Dip Switch Setting - LG MULTI V ARNU363NJA4.AMBBLUS Installation Manual

Vertical air handling unit
Hide thumbs Also See for MULTI V ARNU363NJA4.AMBBLUS:
Table of Contents

Advertisement

Installation

Dip Switch Setting

1. Indoor Unit
Function
SW1
Communication N/A (Default)
SW2
Cycle
SW3
Group Control
Dry Contact
SW4
Mode
SW5
Installation
SW6
Heater linkage N/A
Ventilator link-
age
Vane selection
SW7
(Console)
Region selec-
tion
SW8
Etc.
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
2. Outdoor Unit
In case that the products meet specific conditions, "Auto addressing" function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
※ Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch
Outdoor Unit PCB
24 Vertical Air Handling Unit
Description
N/A (Default)
Selection of Master or
Slave
Selection of Dry
Contact Mode
Fan continuous
operation
Selection of Ventilator
linkage
Selection of up/down
side Vane
Selection tropical
region
Spare
7 segment
Setting Off
-
-
Master
Wired/Wireless remote
controller
selection of Manual or Auto
operation Mode
Continuous operation
Removal
-
Linkage Removal
Up side + Down side Vane
General model
-
Outdoor Unit DIP Switch
Setting On Default
-
Off
-
Off
Slave
Off
Auto
Off
-
Off
-
Off
Working
Up side Vane
Off
Only
Tropical
model
-
Off

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents