Dip Switch Setting - LG ARNU07GTRB4 Installation Manual

Hide thumbs Also See for ARNU07GTRB4:
Table of Contents

Advertisement

DIP Switch Setting

1. Indoor Unit
Function
SW1
Communication
SW2
Cycle
SW3
Group Control
Dry Contact Mode
SW4
SW5
Installation
SW6
Heater linkage
SW7
Ventilator linkage
Vane selection
(Console)
Region selection
SW8
Etc.
CAUTION
!
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
2. Outdoor Unit
In case that the products meet specific conditions, "Auto addressing" function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch
7 segment
Outdoor Unit PCB
Description
N/A (Default)
N/A (Default)
Selection of Master or Slave
Selection of Dry Contact
Mode
Fan continuous operation
N/A
Selection of Ventilator
linkage
Selection of up/down
side vane
Selection tropical region
Spare
Setting Off
-
-
Master
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Continuous operation Removal
-
Linkage Removal
Up side + Down side Vane
General model
-
Outdoor Unit DIP Switch
Installation
Setting On
Default
Off
-
Off
-
Off
Slave
Off
Auto
Off
-
Off
-
Working
Up side Vane
Off
Only
Tropical model
-
Off
Installation Manual 13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents