44
DPI C13 PDU+, DPI C19 PDU+, and DPI C19 3-phase PDU+: Installation and Maintenance Guide
Rated voltage
Rated frequency
Maximum power rating
Circuit breakers
Power cord
Power outlets
1. 220-240 V ac, 32 amps, single-phase
2. 200-208 V ac, 48 amps, single-phase
3. 220-240 V ac, 63 amps, single-phase
4. 220-240 V ac, 32 amps, three-phase Wye
5. 200-208 V ac, 24 amps, single-phase
6. 200-208 V ac, 48 amps, three-phase Delta
7. 200-208 V ac, 48 amps, single-phase
8. 220-240 V ac, 63 amps, single-phase
9. 220-240 V ac, 32 amps, three-phase Wye
10. 200-208 V ac, 48 amps, three-phase Delta
50-60 Hz
1. 7680 VA
2. 9984 VA
3. 15120 VA
4. 23040 VA
5. 4992 VA
6. 17292 VA
7. 9984 VA
8. 15120 VA
9. 23040 VA
10. 17292 VA
Six double-pole branch rated circuit breakers rated
at 20 amps
1. One IEC 309 2P+N+Gnd connector rated at
32 amps
2. One IEC 309 2P+Gnd connector rated at 60
amps
3. One IEC 309 2P+N+Gnd connector rated at
63 amps
4. One IEC 309 3P+N+Gnd connector rated at
32 amps
5. One Nema L6-30P connector rated at 30
amps
6. One IEC 309 3P+Gnd connector rated at 60
amps
7. One IEC 309 2P+Gnd connector rated at 60
amps
8. One IEC 309 2P+N+Gnd connector rated at
63 amps
9. One IEC 309 3P+N+Gnd connector rated at
32 amps
10. One IEC 309 3P+Gnd connector rated at 60
amps
Six IEC 320-C19 outlets rated at 16 amps (VDE) /
20 amps (UL/CSA)
Twelve IEC 320-C13 outlets rated at 10 amps
(VDE) / 15 amps (UL/CSA)