Chapter 5. Using the environmental monitoring probe

The environmental monitoring probe is a connectivity device that enables you to
remotely monitor the temperature, humidity, and status of two contact devices
through a standard Web browser, providing greater power management control and
flexible monitoring.
You can use the environmental monitoring probe with any IBM DPI PDU+ models.
When the environmental monitoring probe is connected to the RJ-45 console
connector on the PDU, temperature and humidity readings are automatically
displayed in the Web interface. To access the readings, you must run the Web
browser and connect to the PDU IP address .

Features

The environmental monitoring probe has the following features:
v Hot-swappable feature simplifies installation by enabling you to install the probe
v Monitors temperature and humidity information of any environment you want to
v Measures temperatures between 0 - 80°C (32 - 176°F) with an accuracy of ±1°C.
v Measures relative humidity between 10 - 90% RH with an accuracy of ±5%.
v Can be located away from the PDU with a CAT5 network cable up to 20 m (65.6
v Monitors the status of the two user-provided contact devices.
v Temperature, humidity and contact closure status can be displayed through a
v User selectable alarm thresholds enable you to define acceptable temperature or
v E-mail notification through simple mail transfer protocol (SMTP) using e-mail
v Changes in contact closure status are logged in the PDU Event History log
v When temperature and humidity values exceed user-selectable limits, the event
© Copyright IBM Corp. 2006
RJ-45
connector
safely without powering down the PDU or loads connected to it.
protect your critical equipment.
ft) long.
Web browser.
humidity limits
client software when acceptable alarm limits are exceeded or contacts status
changes.
is logged in the PDU Event History log.
Evironmental
monitoring
probe
37