Eaton Powerware 9140 Quick Start Manual page 16

7.5-10 kva
Hide thumbs Also See for Powerware 9140:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 13
INSTALLATION
4
EATON Powerware
To install the UPS rail kit:
NOTE The UPS takes up position 1 through position 18 (see Figure 4 on page 6).
1. Using two M5 machine screws and an adapter plate, attach the rail to the front
of the rack (see Figure 4 on page 6).
2. Secure the rail to the rear of the rack with four M5 machine screws and an
adapter plate (see Figure 1).
3. Repeat Steps 1 and 2 for the other rail.
Bottom of Rack or Top of
Other Cabinet
4. To tighten the rail adjustment, assemble four M4 machine screws and four M4
locknuts to the middle of the rail assembly. Tighten using a 7 mm (9/32") nut
driver. See Figure 2.
Repeat for the other rail.
M4 Screws
Figure 2. Tightening the Rail Adjustment (Right Rail Assembly Shown)
®
9140 UPS (7.5–10 kVA) Quick Start
Adapter Plate
Figure 1. Securing the Rear Rail (Right Rail Assembly Shown)
S
164201678 Rev 1
Position 6
Position 5
Position 4
Position 3
Position 2
Position 1
M4 Locknuts