Format For The Write Single Register Command; Request Frame Format; Response Frame Format - Huawei UPS2000 Development Manual

Modbus protocol
Hide thumbs Also See for UPS2000:
Table of Contents

Advertisement

UPS2000-(6 kVA-20 kVA)
Modbus Protocol Development Guide

1.5.5.2 Format for the Write Single Register Command

1.5.5.2.1 Request Frame Format

Byte
Field
Descri
ption

1.5.5.2.2 Response Frame Format

Byte
Field
Descri
ption
Issue 02 (2016-03-10)
0
1
ADDR
CMD
Control
Comma
ler
nd type
address
For example, the request frame is 11 06 2B 15 00 01 52 BA.
11 is the slave device address. 06 is the write single register command. 2B15 is the register address.
0001 is the setting value. 52BA is the CRC checking value.
0
1
ADDR
CMD
Control
Comma
ler
nd type
address
The format of the request and response frames is the same for the write single device command.
For example, the response frame is 11 06 2B 15 00 01 52 BA.
11 is the slave device address. 06 is the write single register command. 2B15 is the register address.
0001 is the setting value. 52BA is the CRC checking value.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
3
4
MSB
LSB
MSB
Register address
Data
2
3
4
MSB
LSB
MSB
Register address
Data
1 Communication Protocol
5
6
7
LSB
LSB
MSB
CRC checking
5
6
7
LSB
LSB
MSB
CRC checking