Huawei UPS2000 Development Manual page 17

Modbus protocol
Hide thumbs Also See for UPS2000:
Table of Contents

Advertisement

UPS2000-(6 kVA-20 kVA)
Modbus Protocol Development Guide
Object ID
0x80-0xFF
Request PDU:
Function Code
MEI Type
ReadDevID Code
Object ID
Request parameter description:
If the identifier data is not suitable for individual responses, you can require several request
and response transactions. The object ID byte provides the first identifier code obtained. For
the first transaction, the client must set the object ID to 0x00 to obtain the start of the device
identifier data. For the subsequent transactions, the client must set the object ID to the value
returned by the previous responded server.
If the object ID does not match any known object, the server points to the object numbered
0x00 (from the start).
For single access, the ReadDevID code is 0x04. The object ID in the requesting process
provides the obtained object identifier code.
If the object ID does not match any known object, the server returns an abnormal code
numbered 0x02 (invalid data address).
Response PDU:
Function Code
MEI Type
ReadDevID Code
Consistency Level
More
Issue 02 (2016-03-10)
Object Name
or
Description
N/A
Function code: 43 (decimal), 0x2B (hexadecimal).
MEI type: The MEI type of 14 (0x0E) assigned to the device identifier port.
The ReadDevID has four access types:
0x01: request to obtain the basic device identifier (stream access)
0x02: request to obtain the normal device identifier (stream access)
0x03: request to obtain the extension device identifier (stream access)
0x04: request to obtain the special device identifier (special access)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Type
N/A
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 Communication Protocol
Mandatory or
Category
Optional
(M/O)
N/A
Extension
0x2B
0x0E
0x01/0x02/0x03/0x04
0x00 to 0xFF
0x2B
0x0E
0x01/0x02/0x03/0x04
N/A
0x00/0xFF
11

Advertisement

Table of Contents
loading