1.0 Description
The DS7461i is a Single Zone Input Module designed to operate with compatible multiplex systems. It provides a supervised input
zone for connection of conventional normally open or normally closed inputs. Each DS7461i occupies one multiplex zone address on
the system. The DS7461i connects to the DS7430, DS7436 Multiplex Expansion Modules or the D8125MUX Multiplex Expansion
Module. For additional DS7461i installation information, refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide
(P/N: F01U003639).
2.0 Specifications
Voltage: 12 VDC nominal
Current : 0.5 mA maximum
Line Impedance:
Operating Temperature Range: +32°F to +122°F (0°C to +50°
C)
Relative Humidity: 0 to 93%
Signaling Line Circuit: Class B
Initiating Circuit: Class B
When used in a fire system, NFPA 72 prohibits this product from sharing a communications bus with non-fire devices.
3.0 Programming
Refer to the control panel's installation guide for multiplex zone (point) programming information.
Refer to Section 6.0 on page 3 for switch settings.
4.0 Installation
After any programming or hardware change, do a functional test of the system as required by local codes.
These instructions assume that the control panel is installed and in proper working condition.
The control panel must be programmed and the DS7461i address switches must be set for the DS7461i to operate.
Program the control panel as described in the control panel's reference guide.
Disconnect power to the control panel before routing wires to connect the DS7461i.
Installation manual
for the
DS7461i Single Zone Input Module
Maximum Impedance: 4.05Ω at +68°F (+20°C) nominal
Maximum Distance
250 ft
600 ft
76 m
193 m
Fire applications require 18 AWG.
Size
22 AWG
18 AWG
0.65 mm
1.02 mm

Advertisement

loading

Summary of Contents for Bosch DS7461i

  • Page 1 1.0 Description The DS7461i is a Single Zone Input Module designed to operate with compatible multiplex systems. It provides a supervised input zone for connection of conventional normally open or normally closed inputs. Each DS7461i occupies one multiplex zone address on the system.
  • Page 2 • Remove the cover of the DS7461i. Press in and up with your thumb and nail directly above the lip of the DS7461i (refer to Figure 1). Figure 1: Removing the Cover • Remove the DS7461i circuit board from the base. Press the circuit board retainer tab and pull the circuit board up and out of the base (refer to Figure 2).
  • Page 3 Set the address switch settings before connecting the DS7461i to the multiplex bus. 1 2 3 4 5 6 7 8 No two DS7461i Single Zone modules may be set to the same address. Having two or more units set to the same address may prevent fault detection or cause multiplex bus failure.
  • Page 4 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 © Bosch Security Systems B.V., 2020 2020.04 Torenallee 49, 5617 BA Eindhoven, Netherlands DS7461i Installation Instructions...