OUTPUT MODE

The M9.10 Dual Analog monitor and transmitter features 2 solid state relays
and 2 mechanical relay in addition to an 2 analog output 4-20mA.
1 SSR , 3 RELAY, 4-20 mA 1 can be assigned to the first input.
2 SSR, 4 RELAY, 4-20 mA 2 can be assigned to the second input.
PROCEDURE FOR OUTPUTS SETTING
- go to the "Options" menu
- enter into the "Outputs activation" sub menu
- enable output(s)
- go to the "Outputs" menu
- set the operating mode for each enabled output
ENTER TO CONFIGURE
Monitor without digital
output activated
Digital outputs can be set in the following way:
ON-OFF MODE (icon reports O-F)
LOW LEVEL
Cond.
Output relaxed
Output energized
14
ENTER TO CONFIGURE
In case a digital output
is enabled, a icon will
appear
Hysteresis
Setpoint
Time
ENTER TO CONFIGURE
In case a digital output
is set, icon reports the
operating mode
ON-OFF MODE (icon reports O-F)
HIGH LEVEL
Cond.
Output relaxed
Output energized
1 PRP
ENTER TO CONFIGURE
In case set digital
output is activated, the
icon will turn to black
Hysteresis
Time