FLS M9.10
DUAL-PARAMETER ANALOG
MONITOR & TRANSMITTER
SAFETY INSTRUCTIONS
General Statements
• Do not install and service the product without following the Instruction
Manual
• This item is designed to be connected to other instruments which can be
hazardous if used improperly. Read and follow all associated instrument
manuals before using with it
• Product installation and wiring connections should only be performed by
qualified staff
• Do not modify product construction
Installation and Commissioning Statements
• Remove power to the instrument before wiring input and output connections
• Do not exceed maximum specifications using the instrument
• To clean the unit, use only chemical compatible products
PACKING LIST
Please verify that the product is complete and without any damage.
The following items must be included:
• M9.10 Dual Analog Input Monitor and Transmitter
• Instruction Manual for M9.10 Dual Analog Input Monitor and Transmitter
1

Advertisement

Table of Contents
loading

Summary of Contents for FIP FLS M9.10

  • Page 1 FLS M9.10 DUAL-PARAMETER ANALOG MONITOR & TRANSMITTER SAFETY INSTRUCTIONS General Statements • Do not install and service the product without following the Instruction Manual • This item is designed to be connected to other instruments which can be hazardous if used improperly. Read and follow all associated instrument manuals before using with it •...
  • Page 2: Technical Data

    DESCRIPTION The new FLS M9.10 is a powerful monitor designed to manage analog and frequency signals (or two analog signals) from every types of device which provide a 4-20mA or a frequency output. M9.10 is equipped with a wide full graphic display 4”...
  • Page 3: Standards And Approvals

    Electrical • Supply Voltage: 12 to 24 VDC ± 10% regulated • Maximum current consumption: 300 mA • FLS hall effect flow Sensor power: - 5 VDC @< 20 mA - Optically isolated from current loop - Short circuit protected •...
  • Page 4: Panel Mounting

    DIMENSIONS PANEL MOUNTING WALL MOUNTING INSTALLATION Mechanical installation Dual Analog Input Monitor and Transmitter M9.10 is available just in one packaging for panel or wall installation. The panel version is installed using the panel mounting kit (M9.SN1), while the wall mounting version is got fixing the panel mounting version on the wall mounting kit (M9.KWX).
  • Page 5: Panel Installation

    Panel installation Fix instrument on the panel rotating by hand the fixing snails (M9.SN1). Wall installation Use the panel mounting kit (M9.SN1) to fix the M9.10 on the dedicated frontal cutout of the wall mounting kit (M9.KWX). Tighten front screws of box and waterproof connectors of cables, internally mount caps on screw sites to get a IP65 watertight installation.
  • Page 6: General Recommendation

    WIRING General recommendation Always ensure the power supply is switched off before working on the device. Make wiring connections according to wiring diagrams. • Terminals accept 26 to 12 AWG (0.08 to 2.5 mm2) • Strip around 10 mm (0.4”) of insulation from the wire tips and tin bare ends to avoid fraying.
  • Page 7: Power Wiring Diagram

    POWER WIRING DIAGRAM Power Supply 12 - 24 VDC + VDC 12 - 24 VDC - VDC LOOP WIRING DIAGRAM...
  • Page 8: Input Wiring Diagram

    INPUT WIRING DIAGRAM Active loop devices Passive loop devices USB PORT A USB port (type B) is available on the M9.10 PCB. The USB connection allows the updating of device software. To update the software you need: USB cable (M9.KUSB), the interface software "FLS Calibration System” and the new updating software for M9.10 which are both downloadable from www.
  • Page 9 Connection to an User User N.O. AC or DC User N.O. N.O. AC or DC AC or DC AC or DC Power Power Power Power User User Imax = 50mA Imax = 50mA Imax = 50mA Imax = 50 lmax = 50mA lmax = 50mA The alarm is off during normal operation and goes ON according to...
  • Page 10: Operational Overview

    OPERATIONAL MENU DIRECTORY OVERVIEW The M9.10 Dual Analog Input Monitor and Transmitter features a full graphic display and a five-button keypad Settings for system set-up, calibration and operation. Full graphic display has a white backlight during standard conditions, a red backlight in case a set alarm is activated (MAX, MIN, WINDOW IN, WINDOW OUT MODE: always with priority), a green backlight in case a external device control is activated (PROPORTIONAL FREQUENCY,...
  • Page 11 MENU LEVEL INPUT 1 INPUT 20 mA* mA INPUT UNIT INPUT 4 mA* INPUT 2 INPUT 1 IN LINE-ADJUSTEMENT* 2 POINT CALIBRATION* INPUT 2 1 SSR* 2 SSR* 3 RELAY* EDIT LEVEL 4 RELAY* 4-20 mA 1* PUSH BUTTON 4-20 mA 2* TEST OUTPUT LANGUAGE FILTER INPUT 1...
  • Page 12 MENU DIRECTORY OPERATIONAL OVERVIEW The M9.10 Dual Analog Input Monitor and Transmitter features a full graphic display and a five-button keypad Settings for system set-up, calibration and operation. Full graphic display has a white backlight during standard conditions, a red backlight in case a set alarm is activated (MAX, MIN, WINDOW IN, WINDOW OUT MODE: always with priority), a green backlight in case a external device control is activated( PROPORTIONAL FREQUENCY,...
  • Page 13 MENU LEVEL INPUT 20 mA mA INPUT UNIT INPUT 1 INPUT 4 mA K FACTOR VALUE INPUT 2 FLOW UNIT VOLUME UNIT IN LINE-ADJUSTEMENT INPUT 1 2 POINT CALIBRATION CORRECTION FACTOR INPUT 2 AUTO CALIBRATION 1 SSR EDIT LEVEL 2 SSR 3 RELAY PUSH BUTTON 4 RELAY...
  • Page 14: Output Mode

    OUTPUT MODE The M9.10 Dual Analog monitor and transmitter features 2 solid state relays and 2 mechanical relay in addition to an 2 analog output 4-20mA. 1 SSR , 3 RELAY, 4-20 mA 1 can be assigned to the first input. 2 SSR, 4 RELAY, 4-20 mA 2 can be assigned to the second input.
  • Page 15 PROPORTIONAL MODE (icon PROPORTIONAL MODE (icon reports PRP) LOW LEVEL reports PRP) HIGH LEVEL Cond. Cond. Prop. Band Set Point I + His Set Point I Set Point I Set Point I + His Prop. Band Relay Relay Prop Prop TIMED MODE (icon reports TMD) TIMED MODE (icon reports TMD) HIGH LEVEL...
  • Page 16 In case frequency input is activated, digital outputs (2 SSR, 4 RELAY) can be set in following way: MIN MODE (icon reports MIN) MAX MODE (icon reports MAX) Flow Flow Hysteresis Setpoint Setpoint Hysteresis Output relaxed Time Time Output relaxed Output energized Output energized WINDOW IN MODE...
  • Page 17: Software Updating

    SOFTWARE UPDATING In order to update the Instrument Software with a New Firmware Release follow the suggested procedures TO UPDATE INSTALLED UNITS - Download the interface software “FLS Calibration System” and the Updated Software on www.flsnet.it - Launch the software "FLS Calibration System" on the laptop - Select OPTION and then UPGRADE FIRMWARE - Confirm the "Firmware Upgrade"...
  • Page 18: Ordering Data

    ORDERING DATA Description Power Wire power Sensor Part No. Output /Name supply Technology Input Panel mount Dual 2*(4-20mA), Parameter M9.10.P1 12 - 24 VDC 3/4 wire 2 * 4-20mA 2*(S.S.R.), Analog 2*(mech. relay) monitor & transmitter Wall mount Dual- 2*(4-20mA), Parameter M9.10.W1 12 - 24 VDC...
  • Page 19 NOTE...
  • Page 20 FIP - Formatura Iniezione Polimeri S.p.A. Loc. Pian di Parata 16015 Casella Genova - Italy Tel. +39 010 96211 Fax +39 010 9621209 www.flsnet.it...