Electrical connection
5.6 Additional system components
Terminal type
X524
Terminal type
Connectable conductor
cross-section
Stripped length
Tool
Tightening torque
X531 - X536
Terminal type
Connectable conductor
cross-section
Stripped length
X500 and X501 DRIVE-CLiQ interfaces
Table 5- 35
Connector Pin
Connector
type
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 units), article number: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
108
Screw terminal
Rigid, flexible
With wire-end ferrule without plastic sleeve
With wire-end ferrule with plastic sleeve
AWG / kcmil
6 ... 7 mm
0.5 × 3 mm screwdriver
0.4 to 0.5 Nm
Spring-loaded terminal
Rigid
Flexible
Flexible with wire-end sleeve without plastic sleeve
Flexible with wire-end ferrule with plastic sleeve
AWG / kcmil
10 mm
X500/X501: DRIVE-CLiQ interfaces
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
DRIVE-CLiQ socket
0.2 ... 2.5 mm
0.2 ... 2.5 mm
0.5 ... 1.5 mm
22 ... 12
0.2 ... 1.5 mm
0.2 ... 1.5 mm
0.25 ... 1.5 mm
0.25 ... 0.75 mm
24 ... 16
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply, max. 450 mA
Electronics ground
Operating Instructions, 09/2019, A5E34382853K