Val Controls IHP24-A Manual

Foundation fieldbus
Hide thumbs Also See for IHP24-A:

Advertisement

USER MANUAL
Foundation Fieldbus
IHP24-A
IHP24-AF
IHP24-BF
Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611
DHP-UM-013
Revision: 4
vc@valcontrols.com • www.valcontrols.com
1/58

Advertisement

Table of Contents
loading

Summary of Contents for Val Controls IHP24-A

  • Page 1 USER MANUAL Foundation Fieldbus IHP24-A IHP24-AF IHP24-BF Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 1/58...
  • Page 2: Table Of Contents

    8.3 Don’t remove power when updating configuration ................57 8.4 Don’t use the MTB Transducer block, in Function block Application ..........57 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 3: General

    The information in this user manual is subject to changes without notice. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 4: Purpose

    It is the purpose of this document, to list specifications, protocol commands and functions in the Foundation Fieldbus communication protocol in Val Controls products. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 5: Specifications

    3.2 Power Ratings FF-Fieldbus – H1 Power Requirements: 9-32 V Current Consumption: < 5mA Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 6: Ff - Fieldbus Connector

    Or check the Internal Modbus Menu parameter settings. ID = 1, Baud rate = 38400, Parity = Even, Stop bits = 1. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 7: Ff - Fieldbus Function Blocks Inside The Val Controls Device

    Resources block, used to describe the characteristics of field devices, such as device name, manufacturer, serial number. There is no input or output parameter for resource block. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 8: Transducer Block

    This block is the linking the Hardware and the Fieldbus Analogue and Discrete Input and Output functions. Values in this block should not be changed. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 9: Ff - Function Blocks Used In Default Setting

    If the IHP24 status is “Ok”, FF-Fieldbus status on the AI channel goes to “Good” If the IHP24 status is “Error”, FF-Fieldbus status on the AI channel goes to “Bad” Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 10 Signal in Val Controls CAS_IN Values: SP – Flow % AO.OUT 0.00% - 100.00% Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 10/58...
  • Page 11 The device goes to its hardware fail position. All solenoids are de-energized. Error Code 801 is logged. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 12: Ff - Other Function Blocks Available But Not Used In Default Setting

    OUT_D Values: Status Device Note: No signals are available on any of the channels. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 13 CAS_IN D Values: Status Note: No signals are available on any of the channels. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 14 It includes a variety of functions, such as set-point adjustment, process parameters (PV) filtering, feed forward and output tracking, etc. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 15: Appendix - Ni-Fbus Configurator Tool

    • Choose ‘Upload Configuration.’ • Press ‘Yes’ • .. now its uploading data from the device to NI-FBUS Configurator. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 16: Changing Node Id From Ni-Fbus

    Do not make a factory reset of the device, since it will reset all parameters in the MTB transducer block and all TAG names and Node ID address. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 17: Appendix - Function Blocks Description

    Permitted: Defines the modes which are allowed for an interface of the block. The permitted mode Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 18 Description: Manufacturer identification number – used by an interface device to locate the DD file for the Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 19 1: Run – Normal state when running 2: Restart Resource 3: Restart with Default – Set the parameters to Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 20 NV parameters to non-volatile memory. Zero means Never. 0 1/32mSek FREE_SPACE [Diagnostic] Length: 4 bytes Read Only Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 20/58...
  • Page 21 MAX_NOTIFY [Alarms] Length: 1 bytes Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 21/58...
  • Page 22 Description: This alert is generated by any change to the static data. BLOCK_ALM [Others] 1: Unacknowledged Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 22/58...
  • Page 23 ACK_OPTION [Alarms] Length: 2 bytes Read Write Value: 0x0000 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 23/58...
  • Page 24 Description: Major revision number of the interoperability test case used to register this device. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 25: Appendix - Transducer Block (Mtb)

    BLOCK_ALM [Others] 1: Unacknowledged 2: Alarm State 3: Time Stamp Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 25/58...
  • Page 26 Val Controls product and fieldbus interface. Do not change SLAVE_ADRESS [Others] Slave Address Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 26/58...
  • Page 27 Value Status: Good, Bad .. Description: Analog Input from sensor SCALE_LOC_IN2 [Others] SCALE_LOC_IN_2 Value FROM_EU100 = 10000 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 27/58...
  • Page 28 Value Function Code = FC03 Read Holding Register Value REGISTER_ADDR_OF_VALUE = 7003 Value REGISTER_ADDR_OF_STATUS = 7103 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 29 “Out of Service” MOD_IN7 [Others] MOD_IN Length: 4 bytes, Float Value: 0.00 – 100.00 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 29/58...
  • Page 30 Val Controls Device SCALE_LOC_OUT1 [Others] SCALE_LOC_OUT1 Value FROM_EU100 = 100 Value FROM_EU0 = 0 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 30/58...
  • Page 31 Length: 1 bytes 1: Value: 0 to 255 Read from Sensor 2: Status - Quality: Good, Bad .. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 32 MOD_OUT_D1 [Others] MOD_OUT_D1 Value: State 0 .. 255 Value Status: Good, Bad .. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 32/58...
  • Page 33 LOC_OUT_D8 [Others] Same as LOC_OUT_D1 Value REGISTER_ADDR_OF_VALUE = 7037 Value REGISTER_ADDR_OF_STATUS = 7037 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 33/58...
  • Page 34: Appendix - Analogue Input Function Block (Ai)

    Length 1 byte Read Write Allowed modes that the target may take on 4: Normal Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 35 5: Simulation Enable/Disable bit Length 1 byte Read Write Description: Allows the transducer analog input or Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 36 Read Write Value % 4: Decimal Point Length 1 byte Read Write Value: 2 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 36/58...
  • Page 37 Description: The channel to get the value to the Block from. L_TYPE [Scaling] Length 1 byte Read Write Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 37/58...
  • Page 38 Length: 1 bytes Read Only 3 Time Stamp: Length: 8 bytes Read Only Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 38/58...
  • Page 39 2: Unacknowledged Length: 2 bytes Read Only 3: Unreported Length: 2 bytes Read Only Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 39/58...
  • Page 40 Read Write Value: 1 #INF Description: The setting for high alarm in engineering units Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 41 Description: The status for high high alarm and its associated time stamp. HI_ALM [Others] 1: Unacknowledged Length 1 byte Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 41/58...
  • Page 42 1: Unacknowledged Length 1 byte Read Write 2: Alarm state Length 1 byte Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 42/58...
  • Page 43 Read Only Description: The status for low low alarm and its associated time stamp. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 44: Appendix - Analogue Output Function Block (Ao)

    3: Permitted Length 1 byte Read Write Allowed modes that the target may take on Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 45 DCS block through a defined link. BKCAL_OUT [Process] 1: Value 2: Status Length 1 byte Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 45/58...
  • Page 46 5: Simulation Enable/Disable bit Length 1 byte Read Write Description: Allows the transducer analog input or Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 47 Alarm Denied – Granting of alarm permission has been reset Local – Granting of local permission has been reset Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 48 3 Time Stamp: Length: 8 bytes Read Only 4 Static Revision: Length: 2 bytes Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 48/58...
  • Page 49 Auto mode. In PV units per second. If the ramp rate is set to zero or the block is Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 50 Description: This indicates the read back of the actual continuous value or other actuator position in transducer units. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 51: Appendix - Discrete Input Function Block (Di)

    The supported I/O option “Fault State to Value” – If a fault occours, the SP Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 52 Length: 2 bytes Read Only Description: This alert is generated by any change to Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com...
  • Page 53: Appendix - Discrete Output Function Block (Do)

    TAG_DESC [Process] Length 32 byte Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 53/58...
  • Page 54 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 55: Appendix - Pid Function Block (Pid)

    6.7 Appendix - PID Function Block (PID) Follows the standard for Fieldbus PID functionality. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 56: Trouble Guide

    2. Advanced → 6.Modbus → 4.Stopbits • Select 1 Remember to save when you leave the menu system. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 57: Important Issues

    If the configuration is downloaded to device this will destroy the configuration and parameters set in the device, so that it can’t connect to the fieldbus anymore. Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com •...
  • Page 58 Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611 DHP-UM-013 Revision: 4 vc@valcontrols.com • www.valcontrols.com 58/58...

This manual is also suitable for:

Ihp24-afIhp24-bf

Table of Contents