To Close The Outdoor Unit; Mounting The Outdoor Unit; To Provide The Installation Structure - Daikin LRYEN10A7Y1 Installation And Operation Manual

Co2 conveni-pack outdoor unit and capacity up unit
Table of Contents

Advertisement

12
×
Electrical component box of the capacity up unit
12.2.3

To close the outdoor unit

NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
1 Reinstall the small front plates:
Outdoor unit:
1
2
Capacity up unit:
1
2
2 Reinstall the front panels:
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1 – 2020.04
a
12
12
3 Attach the small front plates to the front panels:
a
12.3
12.3.1
Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise.
3
4
×
×
a
Outdoor unit
b
Capacity up unit
a
Outdoor unit
b
Capacity up unit

Mounting the outdoor unit

To provide the installation structure

NOTICE
▪ When the installation height of the unit needs to be
increased, do NOT use stands to only support the
corners.
▪ Stands under the unit must be at least 100 mm wide.
NOTICE
The height of the foundation must at least be 150 mm from
the floor. In heavy snowfall areas, this height should be
increased up to the average expected snow level,
depending on the installation place and condition.
12 Unit installation
b
b
Installation and operation manual
15