Lamtec ETAMATIC V Quick Reference
Hide thumbs Also See for ETAMATIC V:

Advertisement

Quick Links

Quick Reference for Endusers
ETAMATIC V
ETAMATIC V S
Sensors and Systems for Combustion Engineering
www.lamtec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ETAMATIC V and is the answer not in the manual?

Questions and answers

Summary of Contents for Lamtec ETAMATIC V

  • Page 1 Quick Reference for Endusers ETAMATIC V ETAMATIC V S Sensors and Systems for Combustion Engineering www.lamtec.de...
  • Page 3: Table Of Contents

    Table of Contents Table of Contents General Information ............3 Validity of these Instructions .
  • Page 4: General Information

    General Information General Information Validity of these Instructions These instructions apply to the following device(s): ETAMATIC V in any configuration. These devices conform to the following standards and regulations: • DIN EN 298: 2012-11 • DIN EN 1643: 2014-09 •...
  • Page 5: Safety

    Safety Safety For Your Safety The following symbols are used in this document to draw the user's attention to important safe- ty information. They are located at points where the information is required. It is essential that the safety information is observed and followed, and that applies particularly to the warnings. DANGER! This draws the user's attention to imminent danger.
  • Page 6: Description

    BT300 must be replaced by authorized personnel. Brief Description The ETAMATIC V positions up to 4 actuators, according to freely programmable curves, in de- pendence on a reference input variable. The "V" version has 4 three-step positioning outputs and the "VS"...
  • Page 7 The release of the combustion with the firing-rate controller is carried out by an output at the ETAMATIC V. A digital signal is the output for activating a relay for the connection with a burn- er sequencer (floating contacts via relay module type 660R0027).
  • Page 8 Connecting the ETAMATIC V The operating unit is to be connected by the 9-p Sub D plug with the ETAMATIC V. Use for it the provided lead with the type no. 663R0430. The data communication runs via the LAMTEC SYSTEM BUS.Alternatively the possibility exists to attach the operating unit at the cable of the...
  • Page 9: Operating Description

    Operating Description Selection of a curve-set First, a signal is given to terminal 58 (ETAMATIC V S) when the burner is to start. The mode indicator changes from "AU" to "BE". The flue gas damper runs "OPEN". Then the pre-venti- lation signal is given.
  • Page 10: Operator Device

    Description Operator Device Select operating modes: UEAN  PARA  O  AUTO  EINS  SPLO Select operating parameters: Status  Firing rate rating  Setpoint  Actual value feedback  Setpoint feedback  Dig- ital inputs Display change: -Compound - Flame inten- sity...
  • Page 11 -compound -flame intensity ** UEAN monitoring processor display PARA parameterisation AUTO automatic EINS clear memory SPLO * only available, if activated in the parameter section ** only available with ETAMATIC V / ETAMATIC V S the option "Integrated Flame Monitor"...
  • Page 12: Operation

    Press keys 3 and 2 to browse through the fault history. NOTICE If it is certain that the ETAMATIC V has carried a voltage at all times since the last fault, it is possible, that from the present output of the running time counter and the current time, to de-...
  • Page 13: Resetting O Errors

    30 sec are stored. They are only stored in the EEPROM once the fault is cleared up or the ETAMATIC V leaves the operating mode or control or base firing rate. How to switch the Display...
  • Page 14: Operation And Display Of The O2 Trim

    Operation Operation and Display of the O2 Trim Press key 15 once, to switch the display to O -trim. When you have switched to "Status", the display shows the O actual value and O setpoint value. The display shows the values in brackets, if O trim is deactivated.
  • Page 15: Displaying Checksums And Safety Times

    NOTICE The total counter refers to the ETAMATIC V 's running time. It starts timing as soon as the unit is connected to a voltage source (this also provides the basis for the fault history). The individual running time counters refer to the burner's running time. They start timing as soon as the burner is in operation with the relevant curve set (flame signal is present).
  • Page 16: Internal Burner Firing Rate Controller

    Moving Screen "Actual Temperature is too high" Press key 12 HAND to override this and start the ETAMATIC V, if the maximum tem- perature has not exceeded. Press key 12 HAND again to switch back to automatic mode.
  • Page 17: Thermostat And Control Range

    Press key MANUAL again to cancel firing rate controller. It is also possible to switch the ETAMATIC V to "Manual Control" with the terminals. By short- circuiting the Pt100 signal (e.g. bridge terminal 19 and 20) the burner firing rate controller is switched off.
  • Page 18: Meaning Of The Display

    Internal Burner Firing Rate Controller Meaning of the Display Display in "FIRING RATE" switch position setpoint actual value regular firing internal rate input firing rate Display in mode "MANUAL" regular firing internal firing rate actual value rate input (via channel 1)
  • Page 19: Appendix

    Description → READY (signal on terminal 58) ZÜ → IGNITION POSITION or IGNITION → SETTING/IGNITION position (same as IGNITION, but ETAMATIC V on SETTING) → BASE FIRING RATE → SETTING/BASE FIRING RATE” (as BASIC FIRING RATE, but ETA- MATIC V on SETTING) →...
  • Page 20: Fault Codes

    Appendix Fault Codes NOTICE The LAMTEC burner controls use different methods to detect fault messages between main processor and watchdog processor: BT300/ETAMATIC/FMS/VMS/FA1: The bus transmission does not generally use different fault numbers to distinguish between watchdog processor and main processor faults. In order to distinguish the main processor fault messages from the watchdog processor fault messages, an offset of 10000 is added to the watchdog processor faults.
  • Page 21 Appendix Fault Restart according to Description Code EN676 1st monitoring band over range too long. Channel: 3 1st monitoring band over range too long. Channel: 4 1st monitoring band under range too long. Channel: 1 1st monitoring band under range too long. Channel: 2 1st monitoring band under range too long.
  • Page 22 Appendix Fault Restart according to Description Code EN676 Programme check time of sequencer expired. Leak check fault: gas pressure still applied. Leak check fault: gas pressure missing. Vent gas line manually. >88 Oil pressure < min !!! Gas > min appears in oil operation. Boiler safety chain dropping.
  • Page 23 Appendix Fault Restart according to Description Code EN676 Seal tightness check: Main Gas 1 leaky. Seal tightness check: Main Gas 1 open for too long. Seal tightness check: Main Gas 2 leaky. Flame monitoring: flame after-burn too long Flame monitoring: flame on again Programme check time exceeded.
  • Page 24: Calling Up The Condition Of The Digital Inputs

    Appendix Calling Up the Condition of the Digital Inputs Switch to "digital inputs" with keys 16 and 17 Meaning of the digital inputs of the ETAMATIC V Signal applies  Signal does not apply ...
  • Page 25: Back View

    SYSTEM BUS Communication interface Fig. 6-3 Back view ETAMATIC V NOTICE PC connection only possible via LAMTEC interface adapter! NOTICE When replacing fuses F3, F4, F5, the following specifications must be observed: - 2 A slow - High breaking capacity according to IEC 60127-2, Sheet 5: 1500A @ 250VAC - Melting Integral I²t <...
  • Page 26: Eu Declaration Of Conformity

    Appendix EU Declaration of Conformity...
  • Page 27 Appendix...
  • Page 28 Appendix...
  • Page 29 Appendix...
  • Page 30 The information in this publication is subject to technical changes. LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG Wiesenstraße 6 D-69190 Walldorf Telefon: +49 (0) 6227 6052-0 info@lamtec.de Telefax: +49 (0) 6227 6052-57 www.lamtec.de Printed in Germany | Copyright  2020...

This manual is also suitable for:

Etamatic v s

Table of Contents