3.4
Location & fixings
IMPORTANT
The unit should never be installed adjacent to a dust source. External fouling
of the condenser fins also leads to high condensing temperatures, and will
reduce the life of the unit.
It is recommended that a clearance of 300 mm from the wall (or the next unit) be maintained
from the unit left and rear panels whereas a clearance of 500 mm is to be maintained from the
unit right, top and front panels (seen facing the front of the unit). Both service access and airflow
have been considered in making these recommendations.
Where multiple units are to be installed in the same location, the contractor needs to consider
each individual case carefully. There can be many variations of unit quantities and available
space and it is not the intention of this manual to go over these here. However, in general terms,
air by-pass around each condenser and between the units should be avoided at all times.
Figure 8: End elevation & elevation views - Single-fan unit
Figure 9: End elevation & elevation views - Dual-fan unit
Ideally, the unit should be mounted level on a solid concrete slab with rubber strips between unit
feet and concrete. However the ZX has also been designed for mounting on suitable brackets for
wall mounting. In this case it is not only equally important that the spatial guidelines given above
C6.1.6/1108-0509/E
17