Table 6 — Eaton LCX9000 Fault Code Descriptions and Corrective Actions (PIC III Controls) (cont)
VFD
ICVC
FAULT
PIC 6
FAULT
CODE ON
FAULT
STATE
VFD HIST
STATE
(PIC III)
SCREEN
16
217
449
17
202
440
22
206
449
24
206
449
25
206
450
26
206
449
29
206
449
31
206
444
36
206
449
37
206
449
38
206
449
39
206
449
40
206
449
41
206
444
42
206
449
43
206
449
44
206
449
FAULT
DESCRIPTION
TYPE
Motor over-
Motor is overloaded
load trip
Motor Amps
Motor underload protection
not sensed.
has tripped.
EEPROM
Parameter save fault
checksum
• faulty operation
fault†
• component failure
Counter
Values displayed on counters
fault
are incorrect.
Micropro-
cessor
• faulty operation
watchdog
• component failure
fault
Start-up
Start-up of the drive has been
prevented
prevented.
The thermistor input of option
Thermistor
board has detected increase
fault*
of the motor temperature.
IGBT Inverter Bridge over-
IGBT
temperature protection has
temperature
detected too high a short term
(hardwire)
overload current. This is a
measured value.
Control Unit can not control
Control unit
Power Unit and vice versa.
Device
• option board or control unit
change
changed.
(same
• same type of board or same
type)†
power rating of drive
Device
• option board or drive added.
added
• drive of same power rating
(same
or
type)†
same type of board added
Device
• option board removed
removed†
• drive removed
Device
Unknown option board or
unknown
drive.
IGBT Inverter Bridge over-
temperature protection has
IGBT
detected too high a short term
temperature
overload current. This is a
calculated value.
Brake resis-
Brake resistor overtempera-
tor overtem-
ture protection has detected
perature*
too heavy braking.
Note: the exceptional fault
data record, see Eaton User
Manual for LCX9000 VFD.
Additional codes:
1 = Encoder 1 channel A is
Encoder
missing
fault
2 = Encoder 1 channel B is
missing
3 = Both encoder 1 channels
are missing
4 = Encoder reversed
• option board or control unit
Device
changed
changed
• option board of different type
(different
or
type)†
different power rating of drive
SOLUTION
Decrease the motor load.
If no motor overload exists,
check the temperature model
parameters.
Attempt to reset.
Check value of counters.
Reset the fault and restart.
Should the fault re-occur, con-
tact Eaton.
Cancel prevention of start-up.
Check motor cooling and
loading Check thermistor con-
nection.
Check loading. Check motor
size.
Change control unit.
Reset
Note: No fault time data
record!
Reset
Note: No fault time data
record!
Reset
Note: No fault time data
record!
Contact Eaton.
Check loading. Check motor
size.
Set the deceleration time lon-
ger. Use external brake resis-
tor.
Check encoder channel con-
nections.
Reset.
Note: No Fault Time Data
Record is made.
11
CORRECTIVE ACTION
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.
Check main Circuit breaker for trip.
Increase Current % imbalance in
VFD CONF (PIC III)/CFGUMVFD
(PIC 6) screen.
Reset the fault and restart.
Should the fault re-occur, contact
Eaton.
If thermistor input of the option board
is not in use, it must be short cir-
cuited.
Check VFD_CONF/CFGUMVFD
(PIC 6) screen.
See Eaton manual for location of con-
trol unit.
Press ICVC reset key.
Check option board.
Check option board.
Check VFD_CONF (PIC III)/CFGUM-
VFD (PIC 6) parameters.
Check VFD_CONF (PIC III)/CFGUM-
VFD (PIC 6) parameters.
Check the encoder board.
Press the reset key.
Note: Application parameter values
restored to default.