Troubleshooting And Leakage Tracing; Troubleshooting Schedule; Leakage Tracing - Swegon COOL DXS Installation And Maintenance Instructions Manual

Cooling unit sizes 12 - 80
Table of Contents

Advertisement

8 Trouble shooting and leakage tracing

8.1 Troubleshooting Schedule

Symptom
Compressor is not operating
Too low cooling capacity
The low pressure switch is swit-
ching off the cooling compressor
The high pressure switch is swit-
ching off the cooling compressor
Signifi cant freezing on the
evaporator.

8.2 Leakage Tracing

Leakage tracing should be carried out at least once per
year as a precaution. The leakage tracing inspection must
be documented.
If the cooling system is leaking, this will become apparent
fi rstly by impaired cooling performance, or if the leakage is
substantial, when the cooling unit does not operate at all.
If you suspect that the cooling system is leaking refriger-
ant, check the level of refrigerant in the sight glass located
on the liquid line of the cooling unit.
If you see continuous and a substantial amount of bub-
bling in the sight glass and the cooling unit operates at ap-
preciably lower capacity than normal, the system is prob-
ably leaking. One or several bubbles appearing when the
cooling unit is started up, operation at reduced capacity or
normal operation need not necessarily indicate a refriger-
ant defi ciency.
If it is bubbling in the sight glass and the cooling unit
operates at appreciably lower capacity, call for qualifi ed
service help.
N.B.! Maintenance work in the refrigerant system is per-
mitted to be carried out only by an accredited inspectorate
(a company with requisite authorisation).
14
www.swegon.com
Possible cause
The voltage has been isolated.
Incorrect phase sequence.
The compressor safety circuit has been broken.
Defective cooling compressor.
The voltage has been isolated.
Incorrect phase sequence.
No airfl ow or too low airfl ow across the evaporator.
Thermostat/control equipment incorrectly set or
defective.
Inadequate refrigerant.
No airfl ow or too low airfl ow across the evaporator.
Defective evaporator
The expansion valve is defective.
The high pressure switch is defective.
No airfl ow or too low airfl ow across the condenser.
Excessively high ambient air temperature
The high pressure switch is defective.
The expansion valve is defective or incorrectly set.
No airfl ow or too low airfl ow across the evaporator.
Defective air cooler
GB.COOLDXS.INS.100507
Remedial measure
Check the operating/safety switch. Check the condi-
tion of the fuses.
Check and change the phase sequence.
Check, reset if needed.
Replace the compressor.
Check the operating/safety switch. Check the condi-
tion of the fuses.
Check and change the phase sequence.
Check the airfl ow.
Adjust the setting or replace faulty components.
The cooling system is leaking. Tighten the leak and
charge with refrigerant.
Check the airfl ow.
Check, replace.
Check, replace.
Check, replace.
Check the airfl ow (condenser coil and fan).
Check the ambient air temperature.
Check, replace.
Check. Replace or adjust setting.
Check the airfl ow.
Check, replace.