Vega VEGAFLEX 81 Operating Instructions Manual page 91

Tdr sensor for continuous level and interface measurement of liquids
Hide thumbs Also See for VEGAFLEX 81:
Table of Contents

Advertisement

The basic number of the input registers is always added to the input register address of VEGAFLEX
81.
For that reason, address 1300 must be entered as register address for 1300 for the RTU Thermo
Electron Autopilot.
Bristol ControlWave Micro
Fig. 43: Connection of VEGAFLEX 81 to RTU Bristol ControlWave Micro
1
VEGAFLEX 81
2
RTU Bristol ControlWave Micro
3
Voltage supply
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The basic number of the input registers is always added to the input register address of VEGAFLEX
81.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave
Micro.
ScadaPack
Fig. 44: Connection of VEGAFLEX 81 to RTU ScadaPack
1
VEGAFLEX 81
2
RTU ScadaPack
3
Voltage supply
VEGAFLEX 81 • Modbus and Levelmaster protocol
1
1
RS 485 on COM1
1 +SV
2 RX-
3 TX-
4 GND
5 RXT
6 TXT
7 not used
8 not used
Vdc
+8
to
GND
Value
9600
2 (FC4)
32-bit registers as 2 16-bit registers
1
COM Part 3 (C3)
RS485
1
2
3
TXD-
TXD+
4
GND
5
Vdc
+8
+30
to
GND
10 Supplement
2
+30
3
6
3
7
8
9
2
91