○ Refer to Figure 7 to select the mid-range nozzle
spray angle for the head type being used.
○ Fire the burner and make sure the combustion
is acceptable and the flame is not impinging on
chamber surfaces.
○ If a shorter flame is needed, select a wider spray
angle. If a longer flame is needed, select a
narrower spray angle.
○ Either hollow or solid spray patterns may be used.
If combustion results are not satisfactory with the
selected spray pattern, try the other pattern.
Figure 7. Nozzle Spray Angles
Recommended nozzle spray angles
"F" head
"L1" & "L2" head
"V1" head

Check/adjust electrodes

Check the electrode tip settings. Adjust if necessary
to comply with the dimensions shown in Figure 8. To
adjust, loosen the electrode clamp screw and slide/rotate
electrodes as necessary. Securely tighten the clamp
screw when finished.

Servicing nozzle line assembly

1. Turn off power to burner before proceeding.
2. Disconnect oil connector tube from nozzle line.
3. Loosen the two screws securing igniter retaining
clips and rotate both clips to release igniter
baseplate. Then tilt igniter back on its hinge.
4. Remove splined nut.
5. "F" head air tube. - Remove nozzle line assembly
from burner, being careful not to damage the
electrodes or insulators while handling. To ease
removal of long assemblies (over 9 inches), rotate
assembly 180° from installed position after pulling
partially out of tube.
6. "L1", "L2", and "V1" head air tubes. - Slide nozzle
line assembly forward (further into air tube) so the
head clears the venturi opening. Then rotate the
nozzle line assembly 90° so the nozzle line end
points up. Pull the nozzle line assembly toward you
and remove assembly from burner.
Figure 8. – Electrode Tip Adjustment
Standard Dimensions for F, L1, and V1 Heads.
5/32" Gap
1/16" Nozzle-to-tip
AFG Burner Manual
70° or 80° nozzle
45°, 60°, or 70° nozzle
45°, 60°, or 70° nozzle
5/16" Above
Center
Spacing
Section: Mount Burner on Appliance
The dimensions shown below are for use with L2 heads
and M series air tube combinations ending with an 'N'
suffix (example: AFG70MDAQ
5/32" Gap
1/8" Nozzle-to-tip
7. To replace the nozzle assembly, reverse the above steps

Low Firing Rate Baffle

The AFG Low Firing Rate Baffle (LFRB) reduces the
air flow and pressure. The LFRB is sometimes used for
firing rates under 1.00 gph as listed in Figure 9. Refer
to the appliance manufacturer's instructions. Do not
omit the LFRB when specified. Omitting the baffle when
specified or installing the baffle when not specified could
result in impaired burner performance.
Figure 9. AFG Reduced Firing Rates (with LFRB)
Burner head type
Low Firing Rate Baffle installed
F0
F3, L1, or L2
F4 or F6
V1

Mount Burner on Appliance

Mounting options

1. Bolt the burner to the appliance using the factory-
mounted flange or an adjustable flange.

Mounting dimensions

1. When using the Beckett universal adjustable flange,
mount the air tube at a 2° downward pitch unless
otherwise specified by the appliance manufacturer.
2. Verify that the air tube installed on the burner
provides the correct insertion depth. See Figure 14,
page 12.
3. The end of the air tube should normally be ¼" back
from the inside wall of the combustion chamber.
Never allow the leading edge of the head assembly
to extend into the chamber, unless otherwise
specified by the heating appliance manufacturer.
Carefully measure the insertion depth when using
an adjustable flange. Verify the insertion depth
when using a welded flange.
N
)
1/4" Above
Center
Spacing
up to 0.65 gph
up to 0.85 gph
up to 0.90 gph
up to 1.00 gph
9