GOLD CGs Gas-Fired Water Boiler — Boiler Manual
10b
Service & maint. — annual start-up
1. Review the
owner.
2. Emphasize the need to perform the maintenance
schedule specified in the
Manual
3. Remind the owner of the need to call in a licensed
contractor should the boiler or system exhibit any
unusual behavior.
4. Remind the owner to follow the proper shutdown
procedure and to schedule an annual start-up at the
beginning of the next heating season.
1. Shut down boiler:
42

Review with owner

User's Information Manual
User's Information
(and in this manual as well).
Cleaning boiler

heating surfaces

The boiler contains ceramic fi ber
and fi berglass materials. Use care
when handling these materials per
instructions on
manual. Failure to comply could
result in severe personal injury.
Follow "
To Turn Off Gas to Appliance
instructions on boiler and
Operating instruc-
.
tions
Do not drain boiler unless it will be exposed
to freezing temperatures. If using antifreeze in
system, do not drain.
2. Follow shutdown procedure.
3. Remove venting system connection to boiler.
with the
4. Remove top jacket panel. Turn back insulation.
5. Remove collector box/transition assembly. Clean
sealant from assembly and sections.
6. Remove radiation plates hanging between sec-
tions.
7. Remove burners from base. Brush and vacuum
burners to remove all dust and lint. Verify that all
burner ports are free of debris.
8. Place newspapers in base of boiler to collect soot.
9. Clean between sections with wire fl ue brush.
10. Remove newspaper and soot. Vacuum or brush base
and surrounding area.
11. Reinstall radiation plates.
12. Replace collector box/transition assembly. Seal with
of this
page 64
sealant. Obtain gas-tight seal to prevent fl ue gas
spillage and carbon monoxide emissions, resulting
in severe personal injury or death.
13. Replace insulation and jacket top panel.
"
14. Start up boiler following Section
and the boiler
of this manual). Excessive sooting indicates im-
proper gas combustion. If found check for proper
combustion and make any necessary adjustments.
of this manual
7
(Section
Operating instructions
Part number 550-110-260/0508
9c

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gold cgs