Service And Maintenance - Weil-McLain GOLD CGS 550-110-260/0508 User Manual

Gas-fired water boilers
Table of Contents

Advertisement

GOLD CGs Gas-Fired Water Boiler — Boiler Manual
10a
Service and maintenance — schedule
Table 5 Service and maintenance schedules
Part number 550-110-260/0508
VERIFY PROPER OPERATION AFTER SERVICING
Service technician
(see following pages for instructions)
Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system (and air piping)
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners, base and inlet air box
• Condensate drain system
Service:
• Inducer motor
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
Check/test:
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
Review:
• Review with owner
Follow the

Service and maintenance

ponent literature shipped with the boiler. Failure to perform the service and maintenance
could result in damage to the boiler or system. Failure to follow the directions in this manual
and component literature could result in severe personal injury, death or substantial property
damage.
Owner maintenance
(see CGs User's Information Manual for instructions)
• Check boiler area
• Check air openings
Daily
• Check boiler pressure/
temperature gauge
• Check boiler interior piping
• Check venting system
• Check air vents
Monthly
• Check boiler relief valve
• Check condensate drain system
• Check automatic air vents (if
used)
• Test low water cutoff (if used)
Periodically
• Clean vent termination/air intake
screens
• Oil inducer motor
Every 6 months
• Operate relief valve
End of season
• Shut down procedure
procedures given throughout this manual and in com-