4. Shut off pump(s).
5. Clean water distribution from dirt and debris. Ensure spray branches and nozzles are in place and clean.
Replace damaged or missing nozzles.
6. Reinstall eliminators and ensure they fit tightly with no gaps.
7. Close the sliding access doors.
8. Start fan(s) and pump(s).
Nozzle spray distribution type for condenser
WATER DISTRIBUTION BRANCHLOK™ SYSTEM
The exclusive BranchLok™ system allows you to inspect and clean out the water distribution branches as well as
the nozzles without the use of any tools. Slide the branch end out of the notch in the support channel and slightly
rotate the branch while pulling it out.
BranchLok™ removable spray system
1. Branch end
2. Support channel
3. Notch
COMBINED INLET SHIELDS
Combined inlet shields are installed at the air inlet side. These will prevent UV light from shining into the sump
water and will reduce the suction of large airborne impurities and debris. In addition, they will prevent water from
splashing out of the air intake side of the unit during fan cycling.
Inspect regularly and remove foreign objects that might impair air passage. Replace broken and missing parts
when necessary. Failure to replace broken shields will result in water loss due to splash out.
You can remove the combined inlet shields by simply unscrewing a single tapper on both ends of the air intake
side. A supporting steel strip can be taken out. This allows simple removal of the combined inlet shields in small
and easy to handle sections allowing full access to the sump section for maintenance. The shipping strap does not
need to be restored afterwards.