pH
pH during initial passivation
Total hardness (as CaCO
3
Total alkalinity (as CaCO
3
Total dissolved solids
Conductivity
Chlorides
Sulfates*
Total suspended solids
Chlorination (as free chlorine / halogen): continuous
Chlorination (as free chlorine / halogen): batch dosing for cleaning &
disinfection
Circulated water quality guidelines for Baltibond
*Note: Higher concentration of sulfates is allowed, provided the sum of chlorides + sulfates parameters does not exceed 650 mg/l for
Baltibond/SST304L.
pH
pH during initial passivation
Total hardness (as CaCO
3
Total alkalinity (as CaCO
3
Total dissolved solids
Conductivity
Chlorides
Sulfates*
Total suspended solids
Chlorination (as free chlorine / halogen): continuous
Chlorination (as free chlorine / halogan): batch dosing for cleaning &
disinfection
*Note: Higher concentration of sulfates is allowed provided the sum of chlorides + sulfates parameters does not exceed 500 mg/l for Baltiplus
protection.
3 Water Care
3 Water Care
)
)
)
)
Circulated water quality guidelines for Baltiplus protection
®
Baltibond
Hybrid Coating and SST304L
6.5 to 9.2
Below 8.2
(for units with HDG coil only)
50 to 750 mg/l
600 mg/l max.
2050 mg/l max.
3300 µS/cm
300 mg/l max.
350 mg/l max.*
25 mg/l max.
1.5 mg/l max.
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.
®
Hybrid Coating
Baltiplus protection
6.5 to 9.0
Below 8.2
50 to 600 mg/l
500 mg/l max.
1500 mg/l max.
2400 µS/cm
250 mg/l max.
250 mg/l max.*
25 mg/l max.
1 mg/l max.
5-15 mg/l max. for 6 hours max.
25 mg/l max. for 2 hours max.
50 mg/l max. for 1 hour max.