Installation; Shut-Off; Pressure Testing; Setting/Adjustment - Danfoss ASV-PV Instructions Manual

Automatic balancing valves
Hide thumbs Also See for ASV-PV:
Table of Contents

Advertisement

DANSK
Strengregulator ASV-PV, ASV-PV+ anvendes
sam-men med afspærrings- og måleventil
ASV-M til regulering af differenstryk i
stigstrenge med radiatorventiler med
forindstilling.
ASV-PV, ASV-PV+ anvendes sam-men med
indreguleringsventil ASV-I, til regulering
af differenstryk og flow i stig-strenge
med radiatorventiler uden for-indstilling
(P/Q - regulering) (fig. 1). ASV-PV, ASV-PV+
holder differenstrykket over stig- strenge
konstant.
Maks. arbejdstryk: ..................................... 16 bar
Differenstryk
over ventilen ............. 0,1-1,5 bar (10-150 kPa)
Maks. gennemstrøm-
ningstemperatur ....................................... 120 °C
Ventil-
Indvendigt
størrelser
gevind
DN 15
Rp ½
DN 20
Rp ¾
DN 25
Rp 1
DN 32
Rp 1¼
DN 40
Rp 1½
DN 50
-
Impulsledning: G 1⁄16
Montering
ASV-PV, ASV-PV+ monteres i strengens
returled-ning med flow'et strømmende i
den ind-støbte pils retning (fig. 3).
Det anbefales at montere et FV filter i
installationens fremløb.
Impulsledningen monteres på strengens
fremløb fx via en ASV-I eller en ASV-M ventil
og gennemskylles inden den monteres på
ASV-PV, ASV-PV+ regulatorens + til-slutning
(fig. 2).
ASV-PV, ASV-PV+ monteres iøvrigt efter
forhol-dene.
For at undgå lækage, skal ventiler med
nippel/omløber efterspændes når
anlægget er kommet i drift.
Afspærring
ASV-PV, ASV-PV+ kan afspærre strengen
ved at dreje håndtaget (1, fig. 2) med uret
til stop.
Trykprøvning
Maks. prøvetryk: ........................................ 25 bar
Bemærk: Under trykprøvning skal sikres,
at det statiske tryk er ens på begge sider af
membranen. Det betyder, at impulsledningen
skal tilsluttes og eventuel nåleventil skal
være åben. Hvis ASV‑P/PV eller ASV‑PV+
er installeret i forbindelse med ASV‑M, kan
begge ventiler være åbne eller lukkede
(begge ventiler skal være i samme possition).
Hvis ASV‑P/PV eller ASV‑PV+ er installeret
i forbindelse med ASV‑I, skal begge
ventiler være åbne. Hvis denne instruktion
ikke overholdes, vil membranen på den
automatiske balanceventil ødelægges.
Indstilling
ASV-PV kan indstilles til at regulere
differenstryk mellem 0,05 og 0,25 bar
(5 og 25 kPa), ASV-PV+ mellem
0,2 og 0,4 bar (20 og 40 kPa). ASV-PV er ved
leveringen indstillet på 0,1 bar (10 kPa),
2
ASV-PV+ på 0,3 bar (30 kPa). Indstil-lingen
kan ændres med 0,01 bar (1 kPa) ved at
dreje indstillingsspindlen (2, fig. 2)
1 omgang. Drejes spindlen med uret øges
indstillingen og omvendt.
Hvis indstillingen ikke kendes, drejes
spindlen med uret til stop. Regulatoren er
nu indstillet på ASV-PV 0,25 bar
(25 kPa), på ASV-PV+ 0,4 bar (40 kPa).
Herefter drejes spindlen mod uret "n"
antal omgange indtil onsket indstilling,
fig. 6.
Bemærk: Spindeln må ikke drejes mere end
20 omgange tilbage, idet den ellers går ud af
indgreb.
Aftapning og påfyldning af vand kan fo-
retages gennem aftapningshanen (luk-ket
fig. 4-1, åben fig. 4-2)
Opstart
Udvendigt
Når der fyldes vand på systemet, skal
gevind
afspærringsventilen i fremløbet (ASV-M/I)
G ¾ A
være lukket. Systemet kan fyldes ved
G 1 A
at åbne afspærringsventilen i ASV-P/
G 1¼ A
PV/PV+ i returledningen, eller gennem
G 1½ A
aftapningshanen på ASV-P/PV/PV+.
Systemet skal udluftes på det højeste sted.
G 1¾ A
G 2½
NB. Hvis denne procedure ikke følges, kan
ASV-PV, ASV-PV+ blive stående i lukke
position.
Fejlfinding
Kontroller følgende hvis streng-regulatoren
ikke fungerer korrekt:
1. Er flowretningen gennem ventilen
korrekt?
2. Er impulsledningen monteret korrekt
og evt. nåleventiler åbne?
3. Er regulatorens afspærring åben?
Tilbehør .....................................................Best. nr.
Impulsledning, 1,5 m ..................... 003L8152
Impulsledning, 5 m ......................... 003L8153
Målestuds for
aftapningshane ................................ 003L8143
Isolering
Den styroporemballage som ventilen er
leveret i, kan anvendes som isolerings-
kappe ved temperaturer op til 80 °C.
Automatic balancing valves ASV-PV and
ASV-PV+ are used together with shut-off
and measuring valve ASV-M to control the
differential pressure in risers where the
radiator valves have presetting facilities.
ASV-PV, ASV-PV+ are also used together
with adjustment valve ASV-I to control
the differential pressure and flow in
risers where the radiator valves have no
presetting facilities (P/Q control), (fig. 1).
ASV-PV, ASV-PV+ maintain constant
differential pressure across the riser.
Max. working pressure ........................... 16 bar
Differential pressure
across valve ............. 0.1 - 1.5 bar (10-150 kPa)
Max. flow temperature ............................ 120 °C
VI.A1.I2.1T © Danfoss 12/2007
ENGLISH
Internal
Valve size
thread
DN 15
Rp ½
DN 20
Rp ¾
DN 25
Rp 1
DN 32
Rp 1¼
DN 40
Rp 1½
DN 50
-
Impulse line: G 1⁄16

Installation

ASV-PV and ASV-PV+ must be installed in
the return pipe. The flow must be in the
direction of the cast-in arrow (fig. 3).
It is recommended that an FV filter be
installed in the system supply pipe. The
impulse tube must be fitted on the flow
pipe, e.g. via an ASV-I or an ASV-M valve.
The tube must be flushed through before
being fitted on the + connection of the
ASV-PV or ASV-PV+ automatic balancing
valves (fig. 2).
ASV-PV or ASV-PV+ must in addition be
installed as determined by installation
conditions. When the system has been in
use for some time, the connections with
external threads should be tightened once
again to minimize the risk for leakage.

Shut-off

Turning the ASV-PV or ASV-PV+ knob fully
clockwise will shut off the riser (1, fig. 2).

Pressure testing

Max. test pressure ................................... 25 bar
Note: When pressure testing you must secure
that both sides of the membrane have the
same static pressure. That means the impulse
tube must be connected and any needle
valves must be open. If ASV‑P/PV or ASV‑PV+
is installed in combination with ASV‑M both
valves can be open or closed (both valves
must be in the same position!). If ASV‑P/PV or
ASV‑PV+ is installed in combination with ASV‑
I both valves must be open. If this instruction
is ignored, the membrane of the automatic
balancing valve might be damaged.

Setting/adjustment

ASV-PV can be set to control the differential
pressure between 0.05 and 0.25 bar (5 and
25 kPa), while ASV-PV+ between 0.2 and 0.4
bar (20 and 40 kPa). ASV-PV is factory-set at
0.1 bar (10 kPa), while ASV-PV+ at 0.3 bar
(30 kPa). The setting can be changed by
0.01 bar (1 kPa) by turning the setting
spindle (2, fig. 2) one full turn. Turning the
spindle clockwise increases the setting;
turning it counterclockwise reduces the
setting.
If the setting is not known, turn the spindle
fully clockwise. The setting on ASV-PV is
now 0.25 bar (25 kPa) and on ASV-PV+
0.4 bar (40 kPa). Now turn the spindle a
number of times ("n") until the required
setting is obtained (fig. 6).
Note: Do not turn the spindle more than 20
turns as it will become disengaged.
The cock (closed, fig. 4‑1 ‑ open, fig. 4‑2) can
be used for water tapping and filling.
External
thread
G ¾ A
G 1 A
G 1¼ A
G 1½ A
G 1¾ A
G 2½
73693410 DH-SMT/SI