System-level diagnostics returns you to the prompt if there are no test failures, or lists the full status of
failures resulting from testing the component.
7. Proceed based on the result of the preceding step.
If the system-level diagnostics tests...
Were completed without any failures
Resulted in some test failures
Then...
a. Clear the status logs: sldiag device
clearstatus
b. Verify that the log was cleared: sldiag
device status
The following default response is displayed:
SLDIAG: No log messages are
present.
c. Exit Maintenance mode on both controllers:
halt
The system displays the LOADER prompt.
Attention: You must exit Maintenance
mode on both controllers before
proceeding any further.
d. Enter the following command on both
controllers at the LOADER prompt: bye
e. Return the node to normal operation:
If your system is
running ETERNUS
AX/HX Series...
With two nodes in the
cluster
With more than two
nodes in the cluster
In a two-node
MetroCluster
configuration
In a stand-alone
configuration
You have completed system-level diagnostics.
Determine the cause of the problem.
| Replacing the chassis |
Then...
Issue these
commands:
node::> cluster
ha modify -
configured true
node::> storage
failover modify
-node node0 -
enabled true
Issue this command:
node::> storage
failover modify
-node node0 -
enabled true
Proceed to the next
step.
The MetroCluster
switchback procedure
is done in the
next task in the
replacement process.
You have no further
steps in this particular
task.
11