Activating The 5-Minute Flush Stop (S1); Activating The Intermittent Flushing (S2); Cleaning The Dirt Filter; Troubleshooting Support - DURAVIT Utronic Operating Instructions Manual

Electronic urinal
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 15

6.1 Activating the 5-minute flush stop (S1)

> Hold the magnetic key in front of the right-hand sensor.
Within approx. 3 seconds, several short signals will sound. Then 1 long signal will sound.
> Remove the magnetic key.
2 short signal tones will sound and then service programme S1 will be selected.

6.2 Activating the intermittent flushing (S2)

> Hold the magnetic key in front of the right-hand sensor.
Within approx. 3 seconds, several short signals will sound. Then 2 long signals will sound.
> Remove the magnetic key.
2 short signal tones will sound and then service programme S2 will be selected.

6.3 Cleaning the dirt filter

The dirt filter can be removed and cleaned without needing to dismantle the stainless steel cover.
A diagram can be found at the end of this document - figures

7. Troubleshooting support

Problem
3 long signal tones without
flushing
No flushing or reduced
flushing
Not possible to start up
If
you
have
any
help@duravit.com.

8. Maintenance

8.1 Monitoring the battery status

If 3  long signal tones sound before flushing occurs, the battery charge level is low. After this
happens, a maximum of 50 – 100 further flushes can occur.
20
Cause
Battery is low or empty.
Dirt filter is not clean.
Angle valve is closed.
Battery is empty.
Hose is pinched or kinked.
No connection between the
control unit and the solenoid
valve.
Solenoid valve is faulty.
Start-up has already occurred. > Perform a reset
Battery is empty.
Power supply cable has been
connected incorrectly.
No mains connection.
Power supply is faulty.
Control unit is faulty.
other
questions,
please
contact
Duravit
.
1
Solution
> Replace the battery.
> Start the system diagnosis
(see chapter 8.2).
> Clean the dirt filter
(see chapter 6.3).
> Open the angle valve.
> Replace the battery.
> Check the hoses.
> Check the connection
cable.
> Replace the solenoid valve.
(see chapter 4.2).
> Replace the battery.
> Connect the power supply
correctly.
> Connect the control unit to
the mains power.
> Replace the power supply.
> Replace the control unit.