Service Connection Guidelines; Gas Inlet Connection; Installation Of Duct Connection Pops - Rinnai Brivis StarPro SP5 Series Installation Manual

Ducted gas heater
Table of Contents

Advertisement

2.5

SERVICE CONNECTION GUIDELINES

2.5.1 Gas Inlet Connection

All piping must be in accordance with AS/NZS 5601 and any local gas regulations.
The connection point for external model heaters is a female G3/4 compression fitting to AS 3688. This is either
located on the outer cabinet of the heater, or supplied loose within the heater.
The connection point for internal model heaters is a male G3/4 compression fitting to AS 3688 located in the
heater cabinet.
A gas cock shall be fitted in the gas line adjacent to the heater and in a convenient location so it can be turned
OFF quickly and easily.
The gas supply shall in no way interfere with any servicing of the heater.
Note: The gas supply must be installed by a licensed gas fitter. The gas pipe and gas meter should be sized so the heater can
maintain its required incoming gas pressure at maximum consumption with all other gas appliances operating at their maximum
capacity at the same time as the heater.
2.5.2 Electrical Power Supply
The heater is pre-wired with a 3-pin plug and lead, and shall be plugged into a standard 10 Amp 220-240 volt fixed
switched socket outlet adjacent to the heater, in a convenient location so it can be turned OFF quickly and easily.
Note: A qualified electrician must install the 220 to 240 volt wiring according to local regulations.
Switch OFF the power and unplug the heater before touching any wiring. If any electrical wiring is damaged, it must
IMPORTANT:
be replaced by the manufacturer, its service agents or an electrically qualified technician, in order to avoid a hazard.
The electricity supply must be 220-240V at 50Hz, and supplied by an authorised power supplier. Generators should
never be used to supply this system as their output may be incompatible with, or prone to damage electronic
components of the heater.
2.6

INSTALLATION OF DUCT CONNECTION POPS

On all SP heaters, the duct connection pops need to be fastened to the heater cabinet as follows:
Insert pops into the hole in the pop plate, ensuring the pop flange is placed over the prescribed wall of the
cabinet, refer to "Table 1. Pop Installation Matrix".
Spread pop flange to fit tightly into the hole in the cabinet (the notch side overlapping the other).
Secure pops with the rivets supplied.
Table 1. Pop Installation
Matrix
Internal Model Cabinet
External Model Cabinet
Brivis
Return Air
No. of Walls
SP5
1
SP6
1
SP5
1
SP6
1
Install Pop
No. of Walls
No Option
No Option
No Option
No Option
9
Supply Air
Install Pop
2
Inner Wall
2
Inner Wall
1
No Option
1
No Option
Ducted Gas Heater IM