Chapter 3 Lightning Protection
3.1
Cabling Reasonably
In the actual network environment, you may need cable outdoors and indoors, and
the requirements for cabling outdoors and indoors are different. A reasonable cabling
system can decrease the damage of induced lightning to devices.
Requirements for Cabling Outdoors
■
Aerial cabling without safeguard is not allowed.
■
It's not allowed cabling down the building to connect network devices in different
■
floors.
Outdoor cables should be buried and paved to the indoor through basement. A piece of
■
steel wire should be paved underground along the pipe and connected to the lightning
protection terminal of the building for shielding. Before connecting the cable to the
device, install a signal lightning arrester on the corresponding port.
When an aerial cable is set up, the cable should be through a metal pipe (15m long
■
at least) before coming into the building. The two ends of this metal pipe should be
grounded. Before connecting the cable to the device, install a signal lightning arrester
on the corresponding port.
It's not necessary to pave STP cables through pipes. The shielded layer of STP cable
■
should be well grounded. Before connecting the cable to the device, install a signal
lightning arrester on the corresponding port.
Note:
It's not recommended using Ethernet cables outdoors. When cabling outdoors,
please use a signal lightning arrester.
Gigabit Business Router
Lightning Protection